background image

iFLOW HVAC INC.

www.iflowhvac.com

18

Item

Display

Range

Default

Minimum Pump Speed

35 ~ 100 %

45 %

Used for advanced adjustment & troubleshooting only. Sets the 

pump speed when a W1 heating call is received.
Minimum Blower Motor 

Speed Control

10 ~ 100 %

20 %

Used for advanced adjustment & troubleshooting only. Sets the 

blower motor speed when a W1 heating call is received.

Reserved

Future 

Cool 

Function

Maximum Pump Speed

35 ~ 100 %

80 %

Used for advanced adjustment & troubleshooting only. Sets the 

pump speed when a W2 heating call is received.
Maximum Blower Motor

Speed Control

10 ~ 100 %

60 %

Used for advanced adjustment & troubleshooting only. Sets the 

blower motor speed when a W2 heating call is received.

Blower ON Delay Time

10 ~ 120  

Seconds 

30 

Seconds

Used for advanced adjustment & troubleshooting only. On a call for 

heat, iFLOW delays blower motor operation until the hydronic coil 

receives heat from the heat source (avoids blowing any cold air).

Blower OFF Delay Time

0 ~ 180 

Seconds

90 

Seconds

Used for advanced adjustment & troubleshooting only. Delays 

blower motor shut off once a call for heat is completed to maximize 

efficiency.  iFLOW continues to circulate the blower to deliver any 

residual coil heat to the home.  Use this function in combination with 

Setting #8 ‘Post Purge Function’ below.  Set #8 to “1”

Post Purge Function

0: OFF   1: ON

1

Used for advanced adjustment & troubleshooting only. Sets 

the pump to continue to run after a heat demand to maximize 

efficiency by extracting all residual heat from the heat source.  

iFLOW continues to circulate the pump to deliver any residual heat 

to the hydronic coil, instead of the heat source post-purging its 

residual waste heat through the exhaust vent. Use this function in 

combination with Setting #7 ‘Blower Off Delay Time’ above.

DHW Priority

0 = ON, 1=OFF

1

Used for advanced adjustment & troubleshooting only. When a flow 

switch on the cold water supply is installed and wired to the iFLOW 

AHU, iFLOW offers DHW Priority. Set whether or not the air handler 

should shut down during periods where there is a demand for 

domestic hot water.  

For cool 

future 

function

Heating Parameter Mode

How to access Heating Parameter:

Push the mode button until the screen reads  

Press ‘ENT’ (enter) to confirm Heating Parameter Mode. Use the 

‘UP’ and ‘DN’ (down) buttons to scroll through the menu of heating 

parameters, numbered 01-16. The 1-3 characters on the right 

indicate the value. Use the up and down buttons to change the 

range of the value and press ‘ENT’ to confirm and ‘MODE’ to exit.

Item

Display

Range

Default

Smart Mode

0= OFF, 1=ON

0

There are 2 way to deliver temperature to the home: 1) Thermostat 

Mode and 2) Smart Mode.  Thermostat mode relies on the room 

thermostat to provide a signal for the air handler to come on and 

turn off.  Smart Mode by-passes the room thermostat and instead 

circulates air continuously through the home and relies on the return 

air temperature to indicate if more or less heating/cooling required. 

The ECM blower is default set at 10% but can be set as low as 5% 

to minimize energy consumption.  See ‘General’ parameter #11 

(Continuous Circulation (‘G’ Call) Blower Speed) to adjust.  WiFi 

mode must be set to ‘internet’. Also use this function when zoning 

but do not have a thermostat for every zone (i.e.: in a retrofit, when 

you cannot run new wire).

Wi-Fi Mode

0=Internet, 

1=Paring

1

There are 2 ways to connect to, and communicate with the iFLOW 

Air Handler using the iFLOW App: through the internet or by pairing.  

Through the internet requires the contractor or homeowner to 

connect the iFLOW Air Handler to the homeowner’s local home Wi-

Fi network.  Pairing connects your smartphone to the air handler 

without a local network (similar to pairing a phone to a car’s stereo).  

In pairing mode, the phone must be in close proximity of the iFLOW 

unit.

Emergency Mode 

0=OFF, 

1=Heat, 

2=Cool

0

Use this setting to override the thermostat and run the heating or 

cooling automatically in an emergency.  Provides emergency heating 

or cooling should there be a thermostat failure.

Schedule Mode

0=OFF, 1=ON

0

Use this mode to select whether you want to use the iFLOW 

scheduling function.

Day

1:SUN 2:MON 

3:TUE 4:WED 

5:THU 6:FRI 

7:SAT

SUN

Set current day of the week

Time

HH:0~24, 

MM:0~59

Current 

Time

Set current time (24 hour clock)

Содержание iFLH-14000W

Страница 1: ...NTELLIGENT SMART IoT TECHNOLOGIES iFLOW HYDRONIC AIR HANDLER NEW GENERATION OF HEATING COOLING iFLOW AHU MANUAL WiFi ZONING Model iFLH 14000W iFLH 16000W iFLH 18000W iFLH 16000D iFLH 18000D iFLH 18000...

Страница 2: ...tankless tank water heater 12 7 Electrical requirements and making connections 12 8 Temperature sensors 12 9 Installing the iFLOW air handler with a Navien tankless water heater 13 10 Zone damper 13...

Страница 3: ...rom all system components and piping prior to start up It is recommended to install purge valves between the air handler and water heater s isolation valves If connected to domestic piping creating an...

Страница 4: ...n any direction Circulating Pump All air handlers require a field supplied single speed or 3 speed pump to be controlled by the iFLOW circulator control This the speed of the pump increases or decreas...

Страница 5: ...ol Fan ON delay Fan OFF heat purge control 5 DHW priority dual mode heating and DHW High low limit safety control air temperature sensor Home freeze protection low ambient temperature sensor Evaporato...

Страница 6: ...r the homeowner and at the same time reduces cooling loads and operating costs 3 Equipment selection and sizing iFLOW air handlers are available in 3 models Please use the following charts to determin...

Страница 7: ...apacity Ton 1 2 1 5 3 2 4 Cabinet Size W x D x H in 14 x 18 3 4 x 27 1 8 16 x 20 3 4 x 27 1 8 18 x 25 3 4 x 29 1 8 mm 356 x 476 x 689 406 x 527 x 689 457 x 654 x 740 Material Cold Roll Steel Sheet Met...

Страница 8: ...28 218 33 572 35 724 37 429 41 357 3 7 33 625 36 256 38 524 41 162 46 456 5 7 140 32 865 39 218 41 625 43 843 48 379 3 7 38 245 42 367 45 412 48 235 53 971 5 5 150 37 536 45 075 47 536 50 327 55 485 3...

Страница 9: ...the outdoor coil A heat pump unit will defrost regularly when frost conditions occur The defrost cycle should be long enough to melt the ice and short enough to be energy efficient When a heat pump go...

Страница 10: ...with all local state provincial and national code requirements that apply to the installation of this equipment The air handler must be installed in such a way that electrical components are protected...

Страница 11: ...heated by the same boiler make up water and low loss header optional Sensor Installation A C Evaporator Temperature Sensor Air outlet on the Evaporator coil See Installation Illustration Page 12 Zone...

Страница 12: ...minal block 7 Route low voltage thermostat wire to the unit connect to thermostat terminal on control board 8 Re secure the front access panel 8 Temperature sensors The iFLOW air handlers come equippe...

Страница 13: ...W AHU at the thermostat connector Connect the communication cable from the iFLOW AHU to the cascade communication port on the Navien Water Heater Panel The parameter P28 of the NAVIEN TL WH should be...

Страница 14: ...age the pump and open the purge valve Verify proper flow direction inlet valve should become warm before the outlet Close the purge valve once flushing is complete Operate the pump for 5 minutes immed...

Страница 15: ...pening Ratio 0 Fully Closed 100 Fully Opened Display Description Explanation Blower Motor Speed Indicates present operation as a percentage of the total fan motor capacity Pump Speed Indicates present...

Страница 16: ...tate Zone 2 Return Damper Opening Ratio 0 Fully Closed 100 Fully Opened Zone 2 Return Temperature Zone 2 Return Air Temperature in F Zone 3 Supply Damper State Zone 3 Supply Damper Opening Ratio 0 Ful...

Страница 17: ...ency Set Up Anti Stagnation 0 24 Hours 24 CSA B214 requires pump circulation once every 24 hours default Some jurisdictions may require a shorter time interval based upon local codes ex if the pump mu...

Страница 18: ...re there is a demand for domestic hot water For cool future function Heating Parameter Mode How to access Heating Parameter Push the mode button until the screen reads Press ENT enter to confirm Heati...

Страница 19: ...3 Zone 2 Blower Speed Heating Mode 0 100 25 Set the blower motor speed for zone 2 as a percentage of the home s total heat loss or CFM requirement see Zone 1 above for details Item Display Range Defau...

Страница 20: ...enter to exit Flow Switch Test Press enter while 11 is flashing Jumper terminals FS on the right side of the control board The display will flash ON if it is working correctly You can also open a hot...

Страница 21: ...supply damper will open close as you increase or decrease the value OPEN 90 80 70 60 50 40 30 20 10 CLOSE Zone 3 Return Damper Test Press enter while 19 is flashing Display will flash OPEN Use UP or...

Страница 22: ...lator The circulating pump is water lubricated and should not require regular maintenance The system control has a pump exercise function during prolonged periods of no heat to avoid seizing Blower Th...

Страница 23: ...3 Wiring Diagrams SZ Field Installation Wiring Diagram SINGLE ZONE Wiring Diagram Do not connect A C with thermostat to the thermostat connector on the control board A C must be connected to A C conne...

Страница 24: ...iFLOW HVAC INC www iflowhvac com SZ Field Installation Wiring Diagram 24 See Details Page 29...

Страница 25: ...c com 25 DZ Field Installation Wiring Diagram DOUBLE ZONE Wiring Diagram Do not connect A C with thermostat to the thermostat connector on the control board A C must be connected to A C connector of c...

Страница 26: ...iFLOW HVAC INC www iflowhvac com DZ Field Installation Wiring Diagram 26 See Details Page 29...

Страница 27: ...ac com 27 QZ Field Installation Wiring Diagram QUAD ZONE Wiring Diagram Do not connect A C with thermostat to the thermostat connector on the control board A C must be connected to A C connector of co...

Страница 28: ...iFLOW HVAC INC www iflowhvac com QZ Field Installation Wiring Diagram 28...

Страница 29: ...NTROL BOARD A C CONDENSING UNIT CONTROL BOARD A C CONDENSING UNIT O C B Y1 C Y2 It should be connected O or B depending on H P type CONTROL BOARD It should be connected O or B depending on H P type CO...

Страница 30: ...iFLOW HVAC INC www iflowhvac com 4 Ladder Diagram 30...

Страница 31: ...against corresponding temperature sensor chart If out of range replace sensor Heat Exchanger 020 H ex Freeze Protection Ambient Temperature below 40 F Resolution Unit will automatically run circulato...

Страница 32: ...Damper Abnormal 122 Supply Zone 3 Damper Abnormal 123 Supply Zone 4 Damper Abnormal 124 Return Zone 1 Damper Abnormal 125 Return Zone 2 Damper Abnormal 126 Return Zone 3 Damper Abnormal 127 Return Zon...

Страница 33: ...ecessary The pump exercise function will help prevent pump seizing Pump is noisy at start up Air is present in the loop If the noise has not diminished after 1 minute purge air in accordance with star...

Страница 34: ...iFLOW HVAC INC www iflowhvac com 34 3 Component Assembly Diagram and Parts Lists Assemble Diagram...

Страница 35: ...0016LC00A iFLH 160000 0018LC00A iFLH 180000 6 1 Left Panel Heat Exchange Guide 0014LG00A iFLH 140000 0016LG00A iFLH 160000 0018LG00A iFLH 180000 6 2 Left Panel Hole Support 0000LS00A iFLH 14 16 18000...

Страница 36: ...ront Cover 0014FC00A iFLH 140000 0016FC00A iFLH 160000 0018FC00A iFLH 180000 2 CTL Board Assembly 30CBA0SZ iFLH 140000 30CBA0DZ iFLH 160000 30CBA0QZ iFLH 180000 3 Blower Assembly 201408CW iFLH 140000...

Страница 37: ...1 2 Blower Assembly Fan 201408BF 201608BF 201808BF 2 Blower Assembly Bracket 2014081B iFLH 140000 2016091B iFLH 160000 2018101B iFLH 180000 3 Blower Motor 2016121A iFLH 14 160000 2018341A iFLH 180000...

Страница 38: ...Model Remark 1 Heat Exchanger 1014004A iFLH 140000 1016004A iFLH 160000 1018004A iFLH 180000 2 A C Eva Temp Sensor 30ETS01B 3 Air Supply Temp Sensor 30ATS01B 4 Air Supply Temp Sensor Bracket 30ATB00A...

Страница 39: ...d panel 30CBP0SZ 2 SZ Control Board Assembly 30CBA0SZ 3 Transformer 402420B 4 Terminal 400T001B 5 Motor Power Cable 50121EON 16AWG 6 Blow Motor Control Cable 50MCTL1A 7 Circulator Control Cabel 50PCTL...

Страница 40: ...d panel 30CBP0SZ 2 DZ Control Board Assembly 30CBA0SZ 3 Transformer 402420B 4 Terminal 400T001B 5 Motor Power Cable 50121EON 16AWG 6 Blow Motor Control Cable 50MCTL1A 7 Circulator Control Cabel 50PCTL...

Страница 41: ...d panel 30CBP0SZ 2 QZ Control Board Assembly 30CBA0SZ 3 Transformer 402420B 4 Terminal 400T001B 5 Motor Power Cable 50121EON 16AWG 6 Blow Motor Control Cable 50MCTL1A 7 Circulator Control Cabel 50PCTL...

Страница 42: ...iFLOW HVAC INC www iflowhvac com 42 4 Installation Diagram iFLOW EZEE Plumbing Kit and iFLOW Stand...

Страница 43: ...iFLOW HVAC INC www iflowhvac com 43 Installation on the wall...

Страница 44: ...iFLOW HVAC INC www iflowhvac com 44...

Страница 45: ...15 60EPFO4A 1 7 Tee with Valve Return 60EPFO5A 1 8 Air Vent 1 2 60EPFO6A 1 9 AHU Inlet Tee Union 60EPFO7A 1 10 Circulator Tee Union w Check Valve 60EPFO8A 1 11 Circulator Grundfos UPS15 58RU 60EPFO9A...

Страница 46: ...eating Application Tankless water Heater DHW Expansion Tank Circulator with Check Valve Heat Pump Check Valve An Scald Valve Cold Water Flow Switch Outdoor Sensor Air Purge Valve Circulator with Check...

Страница 47: ...Check Valve An Scald Valve Cold Water Flow Switch DHW AHU with Tankless Water Heater Space Heating Application Air Purge Valve AHU with Tank Water Heater Space Heating Application Air Elliminator Expa...

Страница 48: ...nkless Boiler Space Heating Application AHU with Combi Boiler Space Heating Application Boiler Make up Water Feeder Air Elliminator Circulator Expansion Tank Tankless Combi Boiler Cold Water DHW Make...

Страница 49: ...ombi Boiler Space Heating Application Expansion Tank Circulator with Check Valve Circulator with Check Valve Cold Water Make up Water Feeder Tankless Combi Boiler Expansion Tank Circulator with Check...

Страница 50: ...r contrary to the instructions included with this unit at the time of shipment or failure to perform maintenance as detailed in aforementioned instructions This warranty will not cover normal maintena...

Страница 51: ...lowhvac com INSTALLATION OPERATION MANUAL iFLOW AIR HANDLER Version 8 6 December 12 2019 CONFORMS TO UL STANDARD 1995 CERTIFIED TO CSA STANDARD C22 2 NO 236 iFLOW HVAC INC 29 Howden Road Toronto ON L3...

Отзывы: