If  the  noise  problem  is  serious,  protect  the  controller  by  using 
termination resistors or shield wires. 

 

1) Termination Resistor   

Termination resistors are used to match impedance of the network to the impedance of the transmission line 

being  used.  When  impedance  is  mismatched,  the  transmitted  signal  is  not  completely  absorbed  by  the 

receiver and a portion of signal is reflected back into the transmission line. 

The decision whether or not to use termination resistors should be based on the cable length and data rate 

used by the communication system.   

For  example,  if  you  use  9,600  baud  rate  and  1,200m  length  of  cable,  the  propagation  velocity  of  cable  is 

0.66  x  speed  of  light  (This  value  is  specified  by  the  cable  manufacturer),  if  we  assume  the  reflections  will 

damp out in three round trip up and down the cable length, the transmitted signal will stabilize 18.6us after 

the leading edge of a bit. Since the data bit is captured in the middle of the bit which is approximately 52us 

after  the  leading  edge  of  a  bit.  The  reflection  stabilizing  time  18.6us  is  much  before  the  center  of  the  bit 

therefore the termination resistors are not required.   

However, if you install the cable to maximum length, the impedance of cable and network is mismatched and 

the  transmitted  signal  is  overlapped  by  the  reflected  signal.  In  this  case,  it  is  recommended  to  add 

termination resistors to the end of the receiver lines. A 120Ω resistor can be used for termination resistor in 

parallel  between  the  receiver  lines  “A”  and  “B”  for  2  wires  RS485  system  or  “RX+”  and  “RX-”  for  4  wires 

RS422 system. A termination resistor of less than 90Ω should not be used and no more than 2 terminations 

should be used in one networking system. Refer to the following picture for information about how to install 

termination resistors.   

 

▶ 

Installation of termination resistors. 

       

<< 

RS485 Communication

 

 

 

 

 

 

 

RS422 Communication 

>>

 

 

 

 

 

Содержание FINGER007 Series

Страница 1: ......

Страница 2: ... discharge b During installation you have to connect the Battery Jumper as shown in Figure 2 so that the Controller can retain data in the event of power failure Figure 1 Battery Jumper location Figure 2 2 Initialization If an LCD module is connected to the iTDC a Apply DC power to the Controller and press the two INT Switches simultaneously Figure 3 b The LCD will display Initialized OK Turn OFF ...

Страница 3: ...hen power off the Controller and return the DIP SW 8 to the ON position Then power on the Controller again Figure7 2 FINGER006 007 Series 505 Series FACE006 007 Series 1 Battery Switch Setting Turn on the backup battery switch as shown below 2 Initialization Hard Initialization 1 Power off the product and connect the yellow and cyan wires of the product to the GND Turn on the power See the diagram...

Страница 4: ...r the password The default password 3141 3 The Mode Selection or READER 1 MODE screen appears 4 Press or until the LCD displays SYS INITIALIZE When it does press 5 Press and the System Initializing message will appear The system is being initialized NOTE All stored data will be lost after initialization 6 After the initialization is completed the LCD displays the SYS INITIALIZE message 7 Use to qu...

Страница 5: ...itted signal will stabilize 18 6us after the leading edge of a bit Since the data bit is captured in the middle of the bit which is approximately 52us after the leading edge of a bit The reflection stabilizing time 18 6us is much before the center of the bit therefore the termination resistors are not required However if you install the cable to maximum length the impedance of cable and network is...

Страница 6: ...hen the voltage level of both ends of shield wire is not equal and this current flow will create noise and interfere to communications For the good grounding we recommend to connecting ONLY one end of shield wire of communication cable to grounding system If you find earth ground nearby then connect one end of shield wire to earth ground If you do not have earth ground nearby then find chassis gro...

Страница 7: ...ter the Password PW Time Schedule TS Reader to be assigned RD and Use of Fingerprint FP Enter appropriate values For fingerprint registration enter 1 in the FP field 8 After the To Register FP Put your FP on message appears and the fingerprint sensor is lit place the finger you d like to register on the fingerprint sensor 9 If the Lift and Put FP message appears lift your finger up and wait until ...

Страница 8: ...r ID is 00000000 For some models it is 0000000000 2 After the Master Password screen appears enter the Master Password The default password is 3141 3 The Mode Selection Reader Mode1 screen appears You ve now entered the SETUP MODE and you can check the internal data and setting values 4 After you re done with the confirmation press to quit the SETUP MENU MODE SELECTION RF ONLY FINGER_007 F1 MM DD ...

Страница 9: ...hen press to move to the F3 SETUP MENU 4 The ID REGISTRATION screen appears 5 Press twice then the ID LIST screen will appear 6 Press then you can check the list of the IDs registered in the device If there s no ID registered the MEMORY EMPTY appears 7 If there is more than one ID registered information such as the ID number password assigned Time Schedule assigned reader number use of fingerprint...

Отзывы: