 CONTROL LINK: indicates if ORP controller is linked to the

electrolysis control board.

 Indication LED of anomalous ORP value: alarm LEDs are

activated automatically when the readings are outside the prefixed
range (650-850 mV). For security reasons, the controller turns-off
the control output when upper limit (850 mV) is exceeded.

 ORP CALIBRATION key: system enters calibration mode when

this key is pressed for a few seconds. The calibration is automatic
and is carried out using a the calibration solution supplied with the
unit (470 mV).

PH-CONTROLLER  

 pH-VALUE display: large LED display showing numerical

indication of the pH reading (green colour).

 pH-SETPOINT display: large LED display showing numerical

indication of the pH setpoint value (red colour).

 Indication LED of product being dosed: selection of the type of

product to dose may be done with a jumper located on the control
board of the unit.

 Indication LED of anomalous pH value: alarm LEDs are

activated automatically when the readings are outside the prefixed
range (6.5-8.5 pH). For security reasons, the controller turns-off
the control output when these limits are exceeded

 pH CALIBRATION key: system enters calibration mode when

this key is pressed for a few seconds. Two calibration modes are
available: “MANUAL”, introducing into the system the present
value of water pH and with no need to manipulate the pH-
electrode; and “STANDARD”, through the buffer calibration
solutions (pH 7.0 and 4.0).supplied with the unit.

 SETPOINT key: allows pH setpoint programming. Built-in

security system avoids accidental programming. 

15

Содержание D-10+

Страница 1: ...SALT ELECTROLYSIS SYSTEM D 10 EN D 18 D 25 D 40 integrated pH ORP controller OPERATION MANUAL D 40...

Страница 2: ......

Страница 3: ...ons 3 SYSTEM DESCRIPTION 3 1 Power supply description 3 2 Remote control 3 3 Electrolysis cell description 4 START UP 5 OPERATION 5 1 Electrolysis system 5 2 Integrated pH controller 5 3 Integrated OR...

Страница 4: ...7 PRACTICAL ADVICES 8 TROUBLESHOOTING 9 WARRANTY 35 36 38 2...

Страница 5: ...elements Power supply with integrated pH ORP controllers Electrolysis cell Models D 10 D 25 Models D 40 Calibration solutions pH 4 0 red pH 7 0 green 470 mV ORP H 035 pH electrode blue PE holder 12mm...

Страница 6: ...ronic polarity reversal D 10 D 18 D 25 D 40 Input ac 220 Vac 50 60 Hz Cable ac H07V K cable 3x1 0 mm2 Consumption ac Fuse 2 A 6x32 mm 3 A 6x32 mm 4 A 6X32 mm 5 A 6X32 mm Output dc 4 5 V 12 A 4 5 V 22...

Страница 7: ...S Control output 220 V 0 5 A max ON OFF triac pH measure range 0 0 9 9 pH control range 7 0 7 8 Precision 0 1 Fuse 0 5 A Calibration Automatic two modes FAST one point calibration STANDARD two point c...

Страница 8: ...uld not be installed outdoors and should be installed a bit distant from the electrolysis cell so that it cannot accidentally suffer water splashes Beware of corrosive atmosphere formation due to pH d...

Страница 9: ...7...

Страница 10: ...valve to regulate the flow must be introduced Prior to installation please consider the following commentaries might be considered o Flow direction marked in the cell must be respected o Recirculation...

Страница 11: ...this situation is extremely unusual it can be easily avoided once the equipment has been installed by locking at opened position the return valve to the swimming pool so it cannot accidentally be mani...

Страница 12: ...older so that it is guaranteed that the sensor located in their ends are always submerged in the water circulating through the pipe Install always the electrodes vertically or with a maximum inclinati...

Страница 13: ...y high current intensity circulating do not modify or cut either the length or section of the supplied cables without making a previous consultation to an authorized IDEGIS distributor The connection...

Страница 14: ...disconnecting the electrolysis system when necessary It is important to continue to test the pool water for chlorine pH and Total Alkalinity and to adjust these values as required The chlorine level c...

Страница 15: ...M Total g grams of chlorine generated since the connection of the unit total count is reseted at 0 00 am Set point shows the programmed chlorine production in grams hour Flow g h shows the chlorine pr...

Страница 16: ...am menus Stop key press this key to STOP the program Run led this led lights up when system program is running Alarm this led lights up when the system reaches an ALARM state ORP CONTROLLER ORP VALUE...

Страница 17: ...owing numerical indication of the pH setpoint value red colour Indication LED of product being dosed selection of the type of product to dose may be done with a jumper located on the control board of...

Страница 18: ...the system mainboard see figure below TERMINAL DESCRIPTION 0 1 OUTPUT CURRENT Range 0 60 mV Not isolated 2 3 OUTPUT VOLTAGE Range 10 V Not isolated 4 5 ALARM Type NO contact Closed when alarm state is...

Страница 19: ...N D 10 D 25 D 40 References Description Model D 10 D 18 D 25 D 40 Electrical contacts protector R 015 07 Closing nut R 015 06 Electrode holder R 015 05 Electrodes R 121 R 122 R 123 R 114 EPDM cell gas...

Страница 20: ...ide without additives like iodides that is apt for human consumption Never add the salt through the cell Add it directly to the swimming pool or into the balance tank When adding the salt and in case...

Страница 21: ...ys will start in the state previous to disconnection 5 1 ELECTROLYSIS SYSTEM 5 1 1 INITIALIZATION When initiating the IDEGIS system at first time it will be necessary to program some system parameters...

Страница 22: ...1 2 PROGRAMMING System configuration parameters may be modified following the next flow sheet IMPORTANT ORP control must be always selected YES if you want to run the IDEGIS system in AUTOMATIC mode 2...

Страница 23: ...5 1 3 RUN ORP CONTROL NOT ACTIVATED MANUAL MODE 21...

Страница 24: ...ORP CONTROL ACTIVATED AUTOMATIC MODE 22...

Страница 25: ...lue appears in the SETPOINT display red colour Only pH values in the range 7 0 7 8 will be able to be input 5 2 2 SELECTION OF THE PRODUCT TO DOSE ACID or ALKALI The IDEGIS SALT ELECTROLYSIS SYSTEM wi...

Страница 26: ...ATION OF RESIDUAL CHLORINE IN THE WATER BUT ITS CAPACITY OF TREATMENT In summary higher ORP mV values bigger disinfection treatment grade 4 If this concept is clear enough it is easy to understand tha...

Страница 27: ...ntration of free chlorine 8 THE ORP SET POINT VALUES FOR EACH POOL WILL BE FIXED IN AN INDIVIDUALIZED WAY IN EACH INSTALLATION Nevertheless a general working range of 700 800 mV may be fixed for pH va...

Страница 28: ...eration with the digits of tenths and units o AUTOMATIC MODE The AUTOMATIC MODE allows to fix quickly the ORP value mV currently present in the water as the setpoint value Maintain the key SET pressed...

Страница 29: ...Overheating of the power supply Contact to our Technical Assistance Service 5 6 4 7 Alarm Stop In all the previous cases the ALARM led in the control panel will blink ALARM MESSAGE DIAGNOSTIC CONTROL...

Страница 30: ...ALARM The integrated pH controller has two ALARM LEDs which are illuminated whenever a pH value outside the range 6 5 8 5 is detected When the controller detects an active alarm control output to the...

Страница 31: ...tem is producing chlorine by doing the following tests While the pool filtration is operational and the salt chlorination system is turned on take a sample of the pool water from the return inlet in t...

Страница 32: ...ion system comprise of a titanium sheet coated with a layer of noble metal oxides The electrolysis processes that take place on their surface produce a progressive wearing down the electrodes do have...

Страница 33: ...solutions IMPORTANT before closing the by pass valves press STOP in the Control Panel of the unit PROCEDURE Be sure the point of insertion of the pH electrode is flooded and the pump is in recirculat...

Страница 34: ...lectrode smoothly so that any water drops that may be adhered to the plastic body are removed and introduce it to the calibration solution pH 7 0 green colour Shake smoothly for a few seconds and pres...

Страница 35: ...easure is unstable during the calibration process code E3 will appear In addition the pH electrode calibration will not be allowed 6 5 CALIBRATION OF THE ORP ELECTRODE The calibration frequency of the...

Страница 36: ...indication in green display will appear If the ORP value detected during the calibration process is very different from the expected one e g defective electrode etc green display will indicate E2 not...

Страница 37: ...er Corrosion of accessories appearance of brown spots High free chlorine concentrations and or pH lower than 7 0 o Adjust pH to 7 2 7 6 o Readjust the production level of the electrolysis system or fi...

Страница 38: ...ply Free chlorine levels in the water are very low Info Chlorine SETPOINT g h TOTAL g FLOW g h 25 25 150 IDEGIS o Check that the system produces chlorine Section 6 1 o Verify that the water chemical p...

Страница 39: ...de Impossible calibration o Polluted or expired buffer solution o Electrode membrane blocked o Electrode fault o Verify the buffer solution is not expired or polluted o Check the membrane is not damag...

Страница 40: ...suffers wearing due to the consumption of the active coating during the electrolysis process Therefore once the operative lifetime of the electrode package has been spent it must be replaced IDEGIS gu...

Страница 41: ...NOTES...

Страница 42: ...NOTES...