Compatibility table (FC4A/5A series -> FC6A Plus)
33
Macro instructions
The available macro instructions for replacing are shown in the table below.
Yes:
Compatible instruction that can be replaced automatically
Indirectly: Instruction that needs to be replaced manually
No:
Instruction that cannot be replaced
Replaceability
Instruction
Remarks
Yes
MACRO
Yes
CWWT, CWRD
If there is no corresponding communication port, communication port 1 will be set.
No
ANST
The FC6A series does not support ANST instructions. However, the Analog Module setting
set by an ANST instruction will be automatically imported to the module configuration editor
when the model is changed. Modules before and after conversion are as follows.
FC4A/5A series No.
FC6A series No.
FC4A-J2A1
FC6A-J2C1
FC4A-J8C1
FC6A-J8A1
FC4A-J4CN1
FC6A-J4CN1
FC4A-J8AT1
FC6A-J8CU1
FC4A-K1A1
FC6A-K2A1
FC4A-K2C1
FC4A-K4A1
FC6A-K4A1
FC4A-L03A1
FC6A-L03CN1
FC4A-L03AP1
Refer to *1 for precautions on model conversion of Analog Modules.
Yes
PULSST
Same with FC4A/5A series.
Yes
PWMST
Same with FC4A/5A series.
Yes
RAMPST
Same with FC4A/5A series.
Yes
ZRNST
Same with FC4A/5A series.
Yes
PIDST
Same with FC4A/5A series.
*1
Precautions on model conversion of Analog Modules
The Analog Module set by an ANST instruction will be automatically imported to the module
configuration editor. However, there are the following precautions. Check the setting after
conversion using the module configuration editor.
• The analog value and status data resister allocation in each channel will change. Allocation in
the FC6A series can be checked using the module configuration editor.
• The filter and scale settings for FC4A-J4CN1, FC4A-J8C1, and FC4A-J8AT1 will be lost.
• The analog input error range settings for FC4A-J4CN1 and FC4A-J8C1 will be lost.
•
If binary data, centigrade, Fahrenheit, and resistance values are selected as the data type,
the analog value range might be changed after conversion.