Technical data
IDEC SmartRelay Manual
299
A.2 Technical data:
FL1E-H12RCC/FL1E-B12RCC
FL1E-H12RCC
FL1E-B12RCC
Power supply
Input voltage
100...240 V AC/DC
Permissible range
85 ... 265 V AC
100 ... 253 V DC
Permissible mains frequency
47 ... 63 Hz
Power consumption
• 100 V AC
• 240 V AC
• 100 V DC
• 240 V DC
25 ... 40 mA
20 ... 30 mA
10 ... 25 mA
6 ... 15 mA
Inrush current
0.46 A at 100 V DC
0.46 A at 100 V AC
0.92 A at 240 V DC
0.92 A at 240 VAC
Voltage failure buffering
• 100 V AC/DC
• 240 V AC/DC
typ. 10 ms
typ. 20 ms
Power loss at
• 100 V AC
• 240 V AC
• 100 V DC
• 240 V DC
2.8 ... 4.6 VA
4.8 ... 7.2 VA
1.1... 2.9 W
1.4 ... 3.6 W
Backup of the real-time clock at 25
C
typ. 80 hours without battery cartridge
typ. 2 years with battery cartridge
Accuracy of the real-time clock
typ.
2 s / day
Digital inputs
Number
8
Electrical isolation
No
High speed inputs
not applicable for this module
Input frequency
• Normal input
• High speed input
• max. 4 Hz
• not applicable for this module
Input voltage L1
• Signal 0
• Signal 1
• Signal 0
• Signal 1
< 40 V AC
> 79 V AC
< 30 V DC
> 79 V DC
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]