Technical data
IDEC SmartRelay Manual
303
Delay time at
• 0 to 1 : 120 V AC
: 240 V AC
: 120 V DC
: 240 V DC
• 1 to 0 : 120 V AC
: 240 V AC
: 120 V DC
: 240 V DC
typ. 50 ms
typ. 30 ms
typ. 25 ms
typ. 15 ms
typ. 65 ms
typ. 105 ms
typ. 95 ms
typ. 125 ms
Line length (unshielded)
100 m
Digital outputs
Number
4
Output type
Relay outputs
Electrical isolation
Yes
Dielectric Strength (between power/input
terminals and output terminals)
2,500 V AC, 1minute
500 V DC, 1 minute
In groups of
1
Control of a digital input
Yes
Continuous current I
th
max. 5 A per relay
Surge current
max. 30 A
Incandescent lamp load (25000 switching
cycles) at
230/240 V AC
100/110 V AC
1000 W
500 W
Fluorescent tubes with ballast (25000
switching cycles)
10 x 58 W (at 230/240 V AC)
Fluorescent tubes, conventionally
compensated
(25000 switching cycles)
1 x 58 W (at 230/240 V AC)
Fluorescent tubes, uncompensated
(25000 switching cycles)
10 x 58 W
(at 230/240 V AC)
Short circuit-proof cos 1
Power protection B16, 600A
Short circuit-proof cos 0.5 to 0.7
Power protection B16, 900A
Derating
none; across the entire temperature range
Parallel output circuits for power increase Not permitted
Protection of output relay (if desired)
max. 16 A,
characteristic B16
Minimum Switching Load
10 mA, 12 V DC
Initial Contact Resistance
100 m
maximum (at 1A, 24V DC)
Mechanical Life
10,000,000 operations minimum
(no load, 10 Hz)