34
insTallaTion
Solar Thermal -
Installation and Servicing
ins
T
alla
T
ion
connecting the collectors to one another
The diagram below is an example of how the collectors can be connected to one another. However, the actual connection may
be different depending on structural conditions. A maximum of 6 collectors may be connected in a series. If a collector panel is
made up of more than 6 collectors, the panel must be connected several times in parallel.
mass flow rate
To ensure the performance of the collector, a specific flow rate of 30 l/m
2
h is to be selected up to a collector panel size of approx.
25m
2
.
pipe Diameters
Dimensions table with a specific flow rate of 30 l/m
2
h
Collector panel size [m
2
]
approx. 5
approx. 7.5
approx. 12.5
approx. 25
Pipe diameter / copper [mm]
10 - 12
15
18
22
Pipe diameter / stainless steel corrugated pipe
DN16
DN20
pressure loss collctor for anti-freeze / water mixture (40% / 60%) at a thermal conducting temperature of 50ºc
Pressure loss curve: ∆p = 0,0001579x
2
+ 0,0274717x
Mass flow rate [kg/h]
0
50
100
150
200
250
300
350
400
450
500
Pressure loss [mbar]
0
1,8
4,3
7,7
11,8
16,7
22,5
29,0
36,3
44,3
53,3
Supply
Return
29 operaTing Tips - solar poWer sysTem Ts8001
207786-2.indd 34
16/02/2012 11:26:14
Содержание Solar Thermal
Страница 59: ...59 Solar Thermal Installation and Servicing ...
Страница 62: ...62 Notes Solar Thermal Installation and Servicing ...
Страница 63: ...63 Notes Solar Thermal Installation and Servicing ...