background image

Page 18

All factory fitted components are tightened during manufacture, however all should 

be checked before installation.

For the control thermostat set points of the immersion heaters for direct heating 

of our cylinders, please refer to page 16 of this manual. The control thermostat for 

indirect heat exchanger heat up of our cylinders are usually set at between 60°C - 65°C. 

During commissioning the actual temperature that the cylinder reaches when the 

thermostat(s) operate should be tested and adjusted so that it achieves a minimum 

of 60°C. This temperature needs to be achieved on a regular basis.  

Check the pressure on the air side of the expansion vessel = 3 bar.  This must be done 

when the water in the cylinder is free to expand in atmospheric pressure or the cylinder 

and relevant pipe work is empty.

Check that the drain cock is closed, and open all the cold and hot water taps and other 

terminal fittings.  Allow the system to fill with water, and to run until there is no air left 

in the system.  Close the taps and inspect the system closely for leaks.

Manually open the Relief Valves one by one and check that water is discharged and 

run freely through the tundish and out at the discharge point.  The pipework should 

accept full bore discharge without overflowing at the tundish, and the valve should 

seat satisfactorily.

In line with good plumbing practice, use of excessive flux should be avoided.  When 

soldering above the cylinder, ensure flux/solder does not contaminate the cylinder 

below, since this can cause corrosion. Flushing should be done performed as per BS 

EN 806:4 2010 section 6.2. 

Allow the cylinder to heat to normal working temperature, then thoroughly flush the 

domestic hot and cold water pipework through each tap.

NOTE:

 If this appliance is to be installed in other than a single domestic dwelling ie. in 

an apartment block or student flats etc., the hot and cold water system will need to be 

disinfected in accordance with BS EB 806:4 2010 section 6.3 and the Water Regulations.

Because the Ideal Pro appliance is stainless steel,  the use of chlorine as the disinfection 

agent can cause damage unless the appliance is adequately flushed and refilled with 

the mains water immediately on completion of the disinfection procedure. Damage 

caused through a failure to do this adequately will not be covered by the warranty.

For the reasons mentioned, we recommend the 

use of a non chlorine based disinfectant such as 

Fernox LP Sterox as manufactured by Cookson 

Electronics when carrying out disinfection of 

systems incorporating these appliances.

Remove the filter from the combination inlet 

group clean and replace.  Refill the system and 

open all hot taps until there is no air in the pipe 

work.  

ENSURE CYLINDER IS DRAINED PRIOR 

TO CHECKING OR REMOVING FILTER FROM 

THE COMBINATION INLET GROUP

.

Allow the cylinder to heat to normal working 

temperature with whatever heat source is to be 

used, and check again for leaks.  The pressure 

relief valve or the P&T valve should not operate 

during the heating cycle. If the P&T valve 

operates before the pressure relief valve due to 

high pressure, check that the inlet control group 

is fitted correctly, and no valve is between the 

inlet control group and the cylinder.

The boiler/heating systems should be filled and 

commissioned in accordance with good practice 

following the guidance in BS 7593:2006/the 

boiler manufacturers instructions. This includes 

adequately flushing the system to remove any 

debris that may have been introduced during 

installation/maintenance.

NOTE

At the time of commissioning, complete all 

relevant sections of the Benchmark Checklist 

located on the inside back pages of this 

document.

This must be completed during commissioning 

and left with the product to meet the Warranty 

conditions offered by Ideal Boilers.

IMPORTANT - DRAIN DOWN PROCEDURE

1  Switch off both the boiler and the immersion heater

2  Open the nearest hot tap and run all hot water until cold, then close it

3  Close the incoming cold main at the stop tap

Hold open the pressure and temperature relief valve until water stops 

discharging into the tundish and leave it open

5  Open the cold taps starting from the highest point and working down to 

the lowest tap, leaving them open

6  When the cold taps have stopped draining, open the hot taps starting from 

the highest and working down to the lowest tap

7  Open the drain cock and ensure the pressure and temperature relief valve 

is held open until the cylinder is empty

INSTALLATION

COMMISSIONING

Содержание PRO Series

Страница 1: ...safety and performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature for speci cation and m...

Страница 2: ...heir safety Children should be supervised at all times to ensure they do not play with the appliance This information is provided to assist generally in the selection of equipment Responsibility for s...

Страница 3: ...ressure Primary heat exchanger Indirect models 6 bar Immersion heater rating 3kW 240V AC All cylinders are manufactured in accordance with the requirements of BS EN 12897 The tundish must be positione...

Страница 4: ...ro Indirect Ideal Pro Indirect is an unvented hot water storage cylinder and is provided with a high efficiency internal primary coil which is designed for use with a gas or oil boiler and is suitable...

Страница 5: ...Dual control overheat stat pocket 22mm 8 Primary return 22mm 9 Primary flow 22mm Part G3 loose components supplied in a separate box A Combination inlet group incorporating pressure reducing valve st...

Страница 6: ...Pressure Regulator 3 bar inlet group c w balance cold supply expansion vessel connection and expansion valve set at 4 5 bar Expansion Vessel size Pre charged to 3 bar Watts kW 24hr Litres kg kg bar L...

Страница 7: ...Peak Immersion Heater High Level Cold Feed 22mm Connection Off Peak Immersion Heater Low Level Volume of On Peak Water Heated Dual Control Overheat Stat 22mm Primary Return Connection 22mm Primary Fl...

Страница 8: ...es 1 shower room Bedsit 0 180 1 bathroom 2 2 180 1 bathroom 4 3 180 1 bathroom separate shower room 6 4 180 1 bathroom 2 separate shower rooms or 2 bathrooms 7 5 180 2 bathrooms separate shower room 7...

Страница 9: ...k is kept to a minimum Shower Fittings Aerated taps are recommended to prevent splashing Any type of shower mixing valve canbeusedaslongasboththehotandcoldsuppliesaremainsfed However allmains pressure...

Страница 10: ...he discharge be of metal and a Be at least one pipe size larger than the nominaloutletsizeofthesafetydeviceunless its total equivalent hydraulic resistance exceeds that of a straight pipe 9m long i e...

Страница 11: ...genuine replacement parts supplied or approved by Ideal Boilers are used All parts are available to approved installers from Ideal Boilers Tundish Hot Outlet To Drain PRV NRV Stop Tap Kitchen Cold Ta...

Страница 12: ...Danger of electrocution before making any adjustments to the thermostat isolate the immersion heater from the mains electricity supply at the fuse spur unit The immersion heater thermostats incorpora...

Страница 13: ...shed by means of a temporary connection between the circuit and a supply pipe provided a Listed double check valve or some other no less effective backflow prevention device is permanently connected a...

Страница 14: ...opposite shows how the blending valve can be piped onsite Figure 1 shows the cold water port of the blending valve connected to the mains cold water supply before the inlet control group This arrangem...

Страница 15: ...with stat Br B 4 core cable Outside Sensor Gr Ideal Logic Heat H with outside sensor For Logic System S ignore pump wiring IN L IN L N E SL2 SL1 Mains In Outside Sensor Ideal Logic Heat H with outside...

Страница 16: ...R Supplied with stat Br B 4 core cable Ideal Logic Heat H without outside sensor For Logic System S ignore pump wiring IN L IN L N E SL2 SL1 Mains In 1 9 8 7 6 5 4 3 2 10 11 12 N L 1 2 3 4 OFF ON OFF...

Страница 17: ...heat Stat Spade connectors required for earth connections Control Stat G Y Br R Supplied with stat Br B 4 core cable 1 9 8 7 6 5 4 3 2 10 11 12 N L 1 2 3 4 OFF ON OFF ON HW CH 1 2 3 4 Room Thermostat...

Страница 18: ...ed and refilled with the mains water immediately on completion of the disinfection procedure Damage caused through a failure to do this adequately will not be covered by the warranty Forthereasonsment...

Страница 19: ...ruction and blockage and are not passing any water 5 Check the condition and if necessary descale the heat exchangers in hard water areas 6 Check that water pressure downstream of pressure reducing va...

Страница 20: ...s electrical ensure that the immersion heaters are isolated from the mains before re setting the energy cut out If the immersion heater s need replacing this should be done with the units supplied fro...

Страница 21: ...tripped Check wiring links continuity and Re set END YES YES YES NO NO NO Switch on Set programmer Re set check wiring plumbing is correct Re set Is all wiring to the controls ok Replace thermostat Re...

Страница 22: ...Clear obstructions Is system free from restrictions blockages YES NO Is pressure reducing valve in combination valve working Clean or replace as required Is expansion vessel charge pressure correct R...

Страница 23: ...6748 3 Inlet group set at 3 bar c w expansion relief valve set at 4 5 bar 1 176750 4 12 litre expansion vessel 1 176751 5 18 litre expansion vessel 1 176752 6 24 litre expansion vessel 1 176753 7 35 l...

Страница 24: ...Page 24...

Страница 25: ...plumbed and pre wired for domestic hot water and one heating zone incorporating a sealed primary filling loop and mains cold feed inlet control components fitted The following pages only provide deta...

Страница 26: ...Drawing No Sheet No For Review Andrew T 14 09 2017 StainlessLite Pro PP Floor Template MIP 926 1 1 awing No MIP 926 P1 Rev No P1 Sh1 1 A3 Tolerance 3 0mm 1 4 1 2 3 4 5a 6 7 8 9 10 Cylinder Hot Outlet...

Страница 27: ...triction or valves fitted in the pipework between the boiler and the primary system safety valve 3 If the primary pipework from the boiler to the safety valve is more than 6 metres we recommend that t...

Страница 28: ...Heating 2 port valve 1 XG083 2 Hot water 2 port valve 1 XG083 3 Automatic primary heating byepass valve 1 XG019 4 Automatic air vent 1 FT434 5 28mm circulator gate valves 1 XB122 6 Filling loop compr...

Страница 29: ...rn Blue Or Gr Motor N OUT IN L Aux Sw HP22 2 PORT HTG VALVE Zone 1 8 N 6 7 Brn Blue Or Gr Motor N OUT IN L Aux Sw HP22 2 PORT DHW VALVE L N 13 N PUMP 15 14 N 11 10 9 PROGRAMMER N L ON ON LINKS WATER H...

Страница 30: ...Page 30...

Страница 31: ...tourbridge West Midlands DY8 1PA TELEPHONE 01384 442611 FAX 01384 442612 Water Savings Water Related Costs Can Be Reduced By Good Plumbing Practice TAPS MIXERS SHOWERS Unregulated 25 30 l m Regulated...

Страница 32: ...As more than one person is required for these products ensure that one person is taking the lead This may be you so ensure that each person that is helping is made aware of the weight and of the item...

Страница 33: ...of any obsolete product and will collect and deliver to any address in England Scotland and Wales excluding all islands Our normal working times excluding Bank Holidays are 8am 6pm Monday to Friday 8...

Страница 34: ...te will then be issued to the customer Heating and Hotwater Industry Council HHIC www centralheating co uk demonstrating compliance with the appropriate Building Regulations and then handed to the cus...

Страница 35: ...me Telephone No Comments Signature SERVICE 05 Date Engineer name Company name Telephone No Comments Signature SERVICE 07 Date Engineer name Company name Telephone No Comments Signature SERVICE 09 Date...

Страница 36: ...ning servicing of central heating systems Ideal Boilers Ltd PO Box 103 National Avenue Kingston Upon Hull HU5 4JN Tel 01482 492251 Fax 01482 448858 Registration No London 322 137 Ideal Technical Helpl...

Страница 37: ......

Страница 38: ......

Страница 39: ...surge in flow may be experienced which disappears as the pressure in the system stabilises This is quite normal with these types of systems and does not indicate a fault In some areas the water will i...

Страница 40: ...and performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature for speci cation and maintenan...

Отзывы: