Indep Combi -
Installation and Servicing
82 aLTERNa TINg ‘ c’ aND ‘0’ - LOW MaINs VOLT agE
Reset Boiler
REsET pROCEDURE - To reset boiler, turn mode knob to reset position and immediately turn knob back to required setting.
83 NO Ch OpERa TION BUT hW WORKs OK
Is the mode knob in the Winter position?
YES
NO
Move the mode knob to the Winter position
Are the Timer and the Room Thermostat switched
on?
YES
NO
Switch the Timer and Room Thermostat On
Are the Radiator Valves Open?
YES
NO
Open the Radiator Valves
Is there 230Vac at (A)?
YES
NO
There is no Voltage from the Timer/Room Stat. This
is not boiler fault. Ensure Voltage is supplied to
boiler by rectifying external wiring.
Replace the Divertor Valve