background image

26

Falcon GTE - 

Installation & Servicing

INSTALLATION

TEST STB

AUT

7

8

9

3

4

6,3 AT

5

6

30

o

c

10

9

8

7

3

4

1

5

6

2

FAL5925

48 COMMISSIONING

IMPORTANT

.  Domestic hot water circuits (if they exist and

heating circuits must have been filled and bled, and leak
tightness tests must have been carried out on them, in
accordance with the instructions for the domestic hot water
calorifier (if existing) and boiler.

1.

Boiler on/off switch.

Position      .....ON

Position     .....OFF

2.

Burner Summer/Winter switch:

Winter 

 starts the burner.

Summer 

 stops the burner.

3.

Heating Pump Summer/Winter Switch:

Winter 

 starts the heating pump.

Summer 

 stops the heating pump.

4.

Three-position switch:

TEST STB:

 when held in the pressed (momentary use)

position it tests the safety thermostat.

Note

. If two stage burner control fitted operation will

continue on 1st stage after 2nd stage cut-off.

The heating pump switch (3) may be put in the
Summer position while performing this test.

AUTO : automatic position,

 used for normal operation

of the boiler.  Use this position if a room thermostat is
fitted.

: Manual Position: 

may be used for normal operation

if two stage burner fitted, but overrides room thermostat
(if fitted) when ON/OFF burner operation fitted.

5.

Boiler thermometer: 

indicates boiler flow water

temperature.

6.

Fuse:  

6.3 amp timed fuse.

7.

Boiler Thermostat:  

Adjustment range 30-90

o

C for ON/

OFF burners and 30-90

o

C 1st Stage, 26-86

o

C 2nd stage

for two stage burners.  (Automatic changeover from
high to low fire at 4

o

 below the flow setting.)

Factory set at 75

o

C.

Built in stops may be reset (See Frame 49).

8.

Hour Run Meter: 

(optional if fitted).

9.

Safety Thermostat: 

(with manual reset) set at 110

o

C.

10.

Location for MB1 module:

 used for DHW control on

Combi models only.

Refer to the following instructions to start up the boiler.

-

the instructions delivered with the burner.

-

the instructions delivered with the domestic hot water
calorifier, (if existing).

49 BOILER THERMOSTAT (Maximum Setting Adjustment)

The boiler thermostat maximum setting is factory set at
75

o

C.  The fixed stop controlling the maximum setting is

adjustable as follows:

1. Carefully remove the control knob.

2. Pull out the pin from the back of the knob.

3. Relocate in the desired position.  Temperature

settings are marked alongside the pin locations.

4. Carefully replace the knob ensuring that the new pin

position is at the correct side of the stop.

5. Rotate the knob to the new desired maximum

position to check correct setting.  (The setting
numbers 3-9 are approximately scaled to represent
30-90

o

C).

80+

5

0+

75+

30-

35-

40-

45

-

50-

90+

70+

80+

5

0+

75+

30-

35-

40-

45

-

50-

90+

70+

fal5934

INST

ALLA

TION

Содержание Falcon GTE 4

Страница 1: ...MIND When replacing any part on this appliance use only spare parts that you can be assured conform to the safety and performance specification that we require Do not use reconditioned or copy parts t...

Страница 2: ...ce It is therefore important that no external control devices e g flue dampers economisers etc are directly connected to these appliances unless covered by these Installation and Servicing Instruction...

Страница 3: ...boilers offering high efficiency operation ease of maintenance fuel flexibility and low emissions in a compact package Suitable for oil or gas operation the Falcon GTE range is supplied in a choice of...

Страница 4: ...5854 Flues and flue structures in buildings BS 5885 Pt1 Gas burners with inputs 60kW and above NOTE TO THE INSTALLER LEAVE THESE INSTRUCTIONS ADJACENT TO THE BOILER BS 6644 Installation of gas fired...

Страница 5: ...need to treat the water contained in all heating and indirect water systems particularly open vented systems It is assumed incorrectly that because boilers are operating in conjunction with what is a...

Страница 6: ...the section and the location of which must comply with local recommendations Refer also to Frame 3 560 987 50 1 189 188 753 608 A B 51 111 214 355 346 205 heating outlet EO heating return EO 3 4 tapp...

Страница 7: ...the advice of the gas supplier should be obtained The temperature within a boiler room shall not exceed 25o C within 100 mm of the floor 32o C at mid height and 40o C within 100 mm of the ceiling Fil...

Страница 8: ...ations or the requirements of the local authority as or water undertakings In general commercial closed pressurised systems are provided with either manual or automatic water make up In both instances...

Страница 9: ...storage cylinder is less than that required by the boiler A combined shunt DHW primary pump sized on the minimum flow to be required MUST be fitted Provided adequate heat dissipation can be achieved a...

Страница 10: ...in BS 6644 and IGE UP 10 whilst BS 5410 Pt 1 similarly applies to OIL fired boilers The table below contains the minimum dimensions of the flue required for each boiler model in order to ensure suffic...

Страница 11: ...The packages are listed in the order in which they are opened for assembly Tools required Phillips head screwdriver Wide flat screwdriver 13 and 17mm spanners hammer Silicone glue JDTE assembly tool S...

Страница 12: ...e groove facing up and fix the height converter with two M10 x 25 bolts serated washers and nuts using a 17mm spanner 14 PREPARING THE SECTIONS 1 Support the rear section with a wooden block 2 Place a...

Страница 13: ...the rear section 3 Hammer in with the help of a small wooden block 4 Proceed likewise for the other intermediate sections FAL5823 3 3 17 ASSEMBLING THE FRONT SECTION AND PULLING UP COMPLETE ASSEMBLY...

Страница 14: ...WITH RIGHT HAND OPENING 3 Screw the threaded bush with the sensor pocket into the upper connection and the plug into the lower connection 4 On the front install the two M10 studs into the holes design...

Страница 15: ...g the door with left hand opening Proceed similarly with the hinges on the left hand side as described in Frames 19 and 20 22 POSITIONING THE FLUE BAFFLES 1 Open the door 2 4 section models place the...

Страница 16: ...od onto the studs and secure with two flanged nuts 1 FAL5832 FAL5833 2 24 INSTALLING THE CONTROL PANEL 1 Place the control panel on the boiler body 2 Position it on the body assembly tie rod 1 2 3 4 F...

Страница 17: ...5 Open the casing package and take out the rear crossbar 6 Secure the crossbar to the rear section on the outside of the lugs with two M8 screws and 2 serrated washers 26 INSTALLING THE INSULATING MA...

Страница 18: ...opean standards proceed as follows 1 Open the control panel two screws and serrated washers on the rear 2 Relocate the burner cable on the opposite side and route it on the outside of the crossbar 3 R...

Страница 19: ...he rear part of the insulation and the side panel FAL5843 3 2 1 31 ASSEMBLING THE LOWER FRONT PANEL To mount the lower front panel proceed as follows 1 Screw the two self tapping screws and serrated w...

Страница 20: ...crews and serrated washers 1 2 FAL5846 34 ASSEMBLING THE REAR PANEL If pipework already made 1 Cut the rear panel with shears along the cut outs 2 First assemble the lower part with four self tapping...

Страница 21: ...self tapping screws and washers 1 2 FAL5848 37 ASSEMBLING THE FRONT PANEL 1 Put notches A on studs B of the lower front panel 2 Position point C in the centring groove of the side panel 3 Push the pa...

Страница 22: ...ctrical control panel equipped with temperature control The control panel carton contains 1 control panel complete with burner connection harness The control panel incorporates a boiler thermostat con...

Страница 23: ...EHOR OPTION Z BEHOR OPTION Z BEHOR OPTION TEMPERATURWAECHTER F R SVR PUMPENLOGIK PUMP LOGIC FAL5852 N L N L N L N AF N 3x 0 75 mm MAINS ROOM STAT not supplied ALARM LIGHT not supplied CH PUMP not supp...

Страница 24: ...onnection block CS Safety contact ECS Domestic hot water control F6 3AT Delayed 6 3 A fuse L Live N Neutral P2 DHW shunt pump RG Connection block TCH Boiler thermostat TS Safety thermostat VA Alarm in...

Страница 25: ...be separate from those of the power supply phase s which are wired direct to the burner via the installer supplied burner mains relay No 8 N Neutral from control panel interrupted by panel ON OFF swit...

Страница 26: ...d 5 Boiler thermometer indicates boiler flow water temperature 6 Fuse 6 3 amp timed fuse 7 Boiler Thermostat Adjustment range 30 90o C for ON OFF burners and 30 90o C 1st Stage 26 86o C 2nd stage for...

Страница 27: ...ion sequence If the burner has failed to light then it will lock out Press the reset button to restart the ignition sequence 10 Operate the boiler for 20 minutes and for gas fired boilers check the ga...

Страница 28: ...ace the flue baffles into the flue ways 4 section models fit 3 flue baffles one each flue 5 8 section models fit 2 flue baffles only in the centre and right hand flues 12 Check the condition of the co...

Страница 29: ...system hot examine all water connections for soundness Check the gas rate and measure the combustion CO CO2 content Complete the boiler log book Carry out functional checks as appropriate 58 SERVICING...

Страница 30: ...30 Falcon GTE Installation Servicing NOTES...

Страница 31: ...31 Falcon GTE Installation Servicing NOTES...

Страница 32: ...uing improvement in the design and performance of its products The right is therefore reserved to vary specification without notice The Ideal Boilers Technical Training Centre offers a series of first...

Отзывы: