background image

Note

.

Natural gas consumption is calculated using a calorific value of 

37.8MJ/m

3

 (1038Btu/ft

3

) gross or 34 MJ/m

3

 (910 Btu/ft

3

) nett at 

15

o

C and 1013.25 mbar.

a

.  For l/s divide the gross heat input (kW) by the gross C.V. of the 

gas (MJ/m

3

)

b.  For ft/h

3

 divide the gross heat input (Btu/h) by the gross C.V. of 

the gas (Btu/ft

3

).

c.  For m

3

/h multiply l/s by 3.6. 

 

d.  1kW = 3412 BTU/hr.

 

e.  1m

3

 = 35.3ft

3

  

f.   1mg/kWh (NOx) = 0.568 ppm DAF (natural gas).
Propane gas consumption is calculated using a calorific value of 

95.7 MJ/m

3

 (2500 Btu/ft.

3

) gross or 88.0 MJ/m

3

 (2300 Btu/ft.

3

) net 

at 15

o

C and 1013.25 mbar.

To obtain the fuel consumption in liquid form divide the above 

figures by 270.

** The value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy ratings of dwellings.  The test data from which it has been calculated have 

been certified by a notified body.

Table 2 General Data

HEALTH & SAFETY DOCUMENT NO. 635

The electricity at work regulations, 1989

.  The manufacturer’s 

notes must NOT be taken, in any way, as overriding statutory 
obligations.

IMPORTANT

. These appliances are CE certified for safety 

and performance.  It is, therefore, important that no external 

control devices, e.g. flue dampers, economisers etc., are 

directly connected to these appliances unless covered by 
these Installation and Servicing Instructions or as otherwise 
recommended by Ideal Boilers in writing.  If in doubt please 
enquire.

Any direct connection of a control device not approved by Ideal 

Boilers could invalidate the certification and the normal appliance 

warranty.  It could also infringe the Gas Safety Regulations and 
the above regulations.

Model

30

30P

40

40P

60

60P

80

80P

100

100P

120

120P

150

Boiler Output

(non-condensing)

Mean 70

°

C

Max

kW

30

30

40

40

60

60

80

80

100

100

120

120

150

Min

kW

6

6

8

8

12

12

16

16

20

20

24

24

30

Boiler Output
(condensing)

Mean 40

°

C

Max

kW

31.5

30.9

42

41.2

63.5

62.1

84.4

82.6

103.9

101.7

124.7

123.3

158

Min

kW

6.5

6.4

8.5

8.3

12.7

12.4

17.2

16.8

21.6

21.3

26

25.7

32.5

Boiler Input

Max Rate

Nett

kW

30.4

30.4

40.5

40.5

60.8

60.7

82

81.9

102.4

102.4

122.9

122.9

153.7

Gross

kW

33.7

33

44.9

44

67.4

66

90.9

88.9

113.6

111.2

136.4

133.4

170.5

Boiler Input

Min Rate

Nett

kW

6.1

6.1

8.1

8.1

12.2

12

16.4

16.2

20.5

20.4

24.6

24.5

30.7

Gross

kW

6.7

6.6

9

8.8

13.5

13.1

18.2

17.5

22.7

22.2

27.3

26.7

34.1

Gas Rate

Max Rate

m

3

/hr

3.2

1.26

4.3

1.69

6.4

2.53

8.7

3.41

10.8

4.35

13

5.23

16.2

Flue Gas Flow Rate 

Max Rate

m

3

/hr

41.3

44.09

54.05

61.68

80.65

88.66

110.1

121.57

140.5

153.6

173.33

183.81

210.7

CO

(±0.5%) *

Max Rate

%

9.76

10.9

10.2

11.2

9.4

11.4

9.3

11.4

9.4

10.8

9.62

11.2

9.44

Min Rate

%

8.56

10.3

8.6

9.7

8.6

10.2

8.7

10.8

8.6

10.1

8.98

10.1

8.51

DB

55.2

55.2

57.7

57.7

59

59

59.9

59.9

62

62

62

62

59

NO

(gross)

weighted

mg/kWh

34.1

52.3

33.2

64.4

35.2

67.7

34.9

63.2

34.8

65.3

33.9

41.6

35.7

Efficiency

Seasonal

%

96.7

97.2

96.2

96.7

96.4

96.9

97.2

97.7

96.7

96.7

96.6

96.6

96.7

**SEDBUK 2009

%

89.6

90.6

89.3

90.3

89.4

90.5

n/a

n/a

n/a

n/a

n/a

n/a

n/a

Max. operating temp sealed sys.

ºC

85

Max. operating temp open vented sys.

ºC

82

*CO

measurements taken using controlled reference natural gas. Readings on mains gas quality may vary 

Model

30

30P

40

40P

60

60P

80

80P

100

100P

120

120P

150

Gas Supply

2H – G20 – 20mbar / 3P - G31 - 37mbar

Gas Supply Connection

G ¾

Flow Connection

G 1¼

Return Connection

G1¼

Max Pressure (sealed sys)

Bar (psi)

6.0 (87)

Maximum Static Head

m

61.0

Electricity Supply

230V - 50Hz

Fuse Rating

A

4.0

Power Consumption

W

81

138

82

149

187

243

240

IP Rating

IPX4D

Nominal flue dia - Concent.

80/125

100/150

Condensate Drain

mm

25

Water Content

L

3.0

5.0

7.0

9.2

Packaged

Kg

53.5

63.5

80

88

Unpackaged (dry weight)

Kg

47.5

57.5

73

81

Table 1 Performance Data (Natural Gas & Propane (P))

6

Installation & Servicing 

SECTION 1 - GENERAL

Содержание EVOMAX 2 30

Страница 1: ...conform to the safety and performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature for spec...

Страница 2: ...7 9 7 13 13 19 5 19 5 Auxiliary Electricity Consumption Full Load elmax kW 0 081 0 081 0 138 0 138 0 082 0 082 Part Load elmin kW 0 027 0 027 0 029 0 029 0 0251 0 0251 Standby PSB kW 0 003 0 003 0 00...

Страница 3: ...lass VIII 1 2 1 5 2 3 4 3 5 5 PRODUCT FICHE The energy efficiency of the package of products provided for in this document may not correspond to its actual energy efficiency once installed in a buildi...

Страница 4: ...4 Installation Servicing...

Страница 5: ...2 31 General Checks 49 2 32 Handing Over 49 2 33 Safety 49 3 SERVICING 50 3 1 Servicing Schedule 50 3 2 Removal of Casing 51 3 3 Removal of Fan and Gas Valve Assembly 52 3 4 Removal of Non Return Val...

Страница 6: ...6 8 8 12 12 16 16 20 20 24 24 30 Boiler Output condensing Mean 40 C Max kW 31 5 30 9 42 41 2 63 5 62 1 84 4 82 6 103 9 101 7 124 7 123 3 158 Min kW 6 5 6 4 8 5 8 3 12 7 12 4 17 2 16 8 21 6 21 3 26 25...

Страница 7: ...ucts of combustion to the outside of the room containing the boiler The combustion air is drawn directly from the room The fan is up stream of the combustion chamber Note Air Inlet Kit must be used II...

Страница 8: ...installed in accordance with the rules in force In GB the installation must be carried out by a suitably qualified Gas Safe registered engineer or in IE by a competent person It must be carried out i...

Страница 9: ...standards listed on page 8 1 8 FLUE INSTALLATION DANGER ONLY USE IDEAL ROOM SEALED FLUE GAS SYSTEMS THE BOILER CE MARK IS VALID ONLY IF THE APPLIANCE IS OPERATED WITH IDEAL ROOM SEALED FLUE KITS OTHER...

Страница 10: ...35 9 28 7 435 180 83 57 30 80 80P 104 2 76 4 57 3 47 8 38 2 750 420 180 125 70 100 100P 95 6 71 7 59 8 47 8 315 134 97 60 120 120P 86 71 7 57 3 218 149 80 150 107 5 89 6 71 7 230 158 85 Not recommende...

Страница 11: ...nd adjacent to the boiler 1 12 CONDENSATE DRAIN Refer to 19 A condensate drain is provided on the boiler This drain must be connected to a drainage point on site All pipework and fittings in the conde...

Страница 12: ...0 120 150 Minimum boiler top clearances for vertical flue 200mm for horizontal flue 370mm for open flue 350mm Flue centre line 194 5 80 125 259 5 100 150 with 100 150 adaptor See Frame 13 Flue centre...

Страница 13: ...er undertakings b The installation should be capable of working with flow temperatures of up to 90o C and a temperature differential of up to 35o C at minimum rate only c All components of the system...

Страница 14: ...er 208 Burner Fixings Kit 230 Fan 231 Gas Valve Kit 232 Venturi 80kW Kit 301 Thermistor Kit 302 Lead Ignition Kit 304 Ignitor Unit 305 Electrode Detection Kit 306 Ignition Electrode Kit 308 Fascia Pla...

Страница 15: ...front of the boiler 5 Remove the packing piece from the top of the boiler 6 Check the contents against the list in Section 2 3 Unpacking Note some items are contained within the top packing piece 7 T...

Страница 16: ...return valve Ensure that during the cutting operation masonry falling outside of the building does not cause damage or personal injury 1 Cut the flue hole ensuring that the hole is square to the wall...

Страница 17: ...flow and return connections to the boiler to prevent the boiler becoming detached The temperature within the boiler room shall not exceed 25 C within 100mm of the floor 32 C at mid height and 40 C wit...

Страница 18: ...al Multiline This permits up to 6 boilers to be connected to a single flue header with a maximum total output of 600kW Other flue header systems should be designed and supplied by a specialist flue co...

Страница 19: ...ue application maximum lengths Model 30 30P 40 40P 60 60P 80 80P 100 100P 120 120P 150 Max flue length m 33 30 17 5 10 10 9 6 Flue Size 80 125 100 150 Vertical flue kit No 220915 220918 60 80 vertical...

Страница 20: ...ded Elbow 100 150 Single 222005 Expander 80 125 100 150 222133 Flue Kits Open Flue Flue Kit Description UIN Wall Bracket 125mm 202242 Wall Bracket 150mm 202243 Open Flue Kit 80 221216 Open Flue Kit 10...

Страница 21: ...60 60P 80 125mm Max flue 17 5m 80 80P 80 125mm 0 5 up to max 12m max flue 60 60P 100 150mm 0 18 up to 30m max flue 80 80P 100 150mm 0 27 up to 35m max flue 100 100P 100 150mm 0 5 up to 14 3m max flue...

Страница 22: ...duct when cutting the flue Note Horizontal flue runs must be angled down between 1 5o 3o towards the boiler to allow the condensate to drain For this reason it is recommended that a support bracket i...

Страница 23: ...roof or balcony level From a surface or a boundary facing the terminal From a terminal facing the terminal From an opening in the car port into the building Vertically from a terminal on the same wall...

Страница 24: ...hieved by cascading up to six boilers Boilers can be fitted side by side using the standard height frame and header kits Low Height Frame and Header Kit Heat output to a maximum of 600kW can be achiev...

Страница 25: ...inage pipe should only be considered after exhausting all internal termination options as described previously An external system must terminate at a suitable foul water discharge point or purpose des...

Страница 26: ...h a 75mm trap and visible air break 2 rows of three 12mm holes 25mm centres 50mm from the bottom of the tube facing away from the house minimum gradient 1 19 Minimum connection height up to 3 storeys...

Страница 27: ...ction 1 13 for details of the position of the gas connection A MINIMUM working gas pressure of 17 5 mbar 7 w g must be available at the boiler inlet for natural gas and minimum of 32mbar for propane w...

Страница 28: ...PC Boiler run S OT or P2 P PC2 Room S RT SC Boiler fault Outside S OT P1 0 10V P PC Tank S HWS or P2 SL1 RT PC P3 P HWSC SL2 TS HWS Standalone Boiler Partial Hydraulics Single Boiler with a CT Pump Ci...

Страница 29: ...CT1 P1 0 10V V CT1 SL2 TS HWS or P2 S OT or P2 Tank S RT CT2 P1 0 10V Opentherm1 or SL1 Opentherm2 or SL2 Boiler CT Pump Circuit CT Pump Circuit Single Boiler with CT and HWS Zone Circuits S RT PC1 RT...

Страница 30: ...One per heating circuit Modulating sequencer kit an external BMS an outside temperature sensor Optional Room Temperature sensor kit one for each heating circuit configured Optional Header Temperature...

Страница 31: ...V 50Hz Typical setting SL1 Heating Circuit 1 SL2 Heating Circuit 2 DHW l3 Optional Interlock input 230V 50Hz l4 Auxiliary Mains Supply Output 230V 50Hz Live Neutral I5 Multifunction Volts Free Relay O...

Страница 32: ...ns supply preferable through the same isolator External controls via switched live demand Boiler Pump controlled directly from MFR1 I1 I2 I3 I4 I5 I6 1 2 3 1 2 3 4 1 2 1 2 1 2 3 4 5 6 1 2 3 4 L N PE S...

Страница 33: ...r pump controlled via remote volts free enabled from MFR1 External controls via OpenTherm Master Boiler Pump speed control via 0 10V output I1 I2 I3 I4 I5 I6 I7 I8 I9 I10 1 2 3 1 2 3 4 1 2 1 2 1 2 3 4...

Страница 34: ...ls via Switched Live or OpenTherm or Room temperature sensors for Two Heating Circuits Heating Circuit Pumps controlled directly from MFR1 and MFR2 I1 I2 I3 I4 I5 I6 I8 I9 I10 1 2 3 1 2 3 4 1 2 1 2 1...

Страница 35: ...B GAS INSTALLATION 1 The whole of the gas installation including the meter should be inspected and tested for soundness and then purged in accordance with the recommendations of the relevant standard...

Страница 36: ...nd highlight the first menu item Enter the highlighted menu sub menu or parameter if in a menu or sub menu If in a parameter setting select a parameter which will then flash for adjustment once adjust...

Страница 37: ...t with the available heating circuits so that they may have HC numbers allocated and then later configured If any heating circuits are required for the boiler then number them sequentially from 1 If t...

Страница 38: ...em in any HC s or DHW circuits Hydraulic Separation If the boiler has Hydraulic Separation from the intermediate or final circuits in the heating system then set this Option to Yes System Pump If the...

Страница 39: ...mperature setpoint Switched Live 1 Input Function The SL1 input can be configured as a Plant function if this is not required select None Where is your shunt pump None PWM 0 10V MFR1 Where is your shu...

Страница 40: ...00 00 Done Single Friday Period 1 06 00 22 00 Period 2 00 00 00 00 Period 3 00 00 00 00 Done Single Saturday Period 1 06 00 22 00 Period 2 00 00 00 00 Period 3 00 00 00 00 Done Single Sunday Period 1...

Страница 41: ...on indication Holidays Period 2 Start 01 01 2000 End 01 01 2000 Done Holidays Period 1 Start 01 01 2000 End 01 01 2000 Done Configure holiday prog No Yes Configure holiday prog No Yes Select loc n of...

Страница 42: ...urn to Note The boiler number now has a tick next to it showing that it has been configured If you completed the boiler configuration select Done Boiler fault indication None PWM 0 10V MFR1 Local boil...

Страница 43: ...ture unless specific configuration options are chosen Switched Live 1 input function The SL1 input can be configured as a HC function if this is not required select None Select loc n of HC pump None P...

Страница 44: ...00 00 00 00 Done Multiple Mon Fri Period 1 06 00 22 00 Period 2 00 00 00 00 Period 3 00 00 00 00 Done Multiple Mon Fri Period 1 06 00 22 00 Period 2 00 00 00 00 Period 3 00 00 00 00 Done Configure hol...

Страница 45: ...ist Otherwise set to None For weekday set the following parameters followed by Done Then set the desired Antilegionalla temperature followed by Done Configure pump protection No Yes Configure pump pro...

Страница 46: ...Period 3 00 00 00 00 Done Single Tuesday Period 1 06 00 22 00 Period 2 00 00 00 00 Period 3 00 00 00 00 Done Single Wednesday Period 1 06 00 22 00 Period 2 00 00 00 00 Period 3 00 00 00 00 Done Singl...

Страница 47: ...t configuration select Done The system will now reboot The boiler configuration is now complete and the display will show the boiler status screen IDEAL Evomax 2 120kW Operation Off Flow temp 0 0 C Fl...

Страница 48: ...the ignition sequence If after 5 attempts the boiler has failed to light then it will lock out Press the reset button to restart the ignition sequence 8 Operate the boiler for 10 minutes and check the...

Страница 49: ...HANDING OVER IMPORTANT Point out to the owner that the boiler must have regular maintenance and cleaning at least annually in order to ensure reliable and efficient operation Regular attention will al...

Страница 50: ...the case and the gas input is at least 90 of the nominal once compliance with the note above is ensured then no further action need be taken If not proceed to 4 4 Remove and clean the burner Refer to...

Страница 51: ...t the panel to remove 3 Lower the control panel to the service position 3 2 REMOVAL OF CASING Side Panels Note Removal of side panels is not required for normal service 4 Remove the screws from the to...

Страница 52: ...reverse order replacing all gaskets MODEL 150 1 Refer to Section 2 33 2 Remove the upper front panel Refer to Section 3 2 3 Disconnect the condensate pipe from the upper flue elbow 4 Remove the three...

Страница 53: ...2 3 Remove the fan and gas valve assembly Refer to Section 3 3 4 Remove the four or six screws and the two extended nuts securing the burner to release the burner body 5 Lift the burner body by lifti...

Страница 54: ...o Section 3 2 3 Prepare boiler for possible condensate spillage during the process 4 Remove the two screws from the helmholtz sump cover and pull away from the boiler 5 Scrape out any deposits 6 Reass...

Страница 55: ...i to the fan for 30 40 60 100 120 5 Remove the extended nuts holding the venturi to the fan 80 only 6 Remove the screws retaining the fan plate 80 only 7 Transfer venturi and gas valve assembly to the...

Страница 56: ...fixing screws 100 120 150 only Refer to Section 3 9 6 Remove the four screws retaining the gas valve 100 120 150 7 Remove the 4 screws retaining the inlet flange to gas valve transfer to new valve 8...

Страница 57: ...Section 2 33 2 Remove the front panel Refer to Section 3 2 3 Pull off the spark lead and earth connection 4 Remove the two retaining cap head screws 5 Pull out the electrode and pull off the old gask...

Страница 58: ...lectrical connections from the switch 5 Unscrew the water pressure switch 6 Refit new switch 7 Connect electrical connections 8 Refill the system ensuring all the air escapes via the air vent 9 Reasse...

Страница 59: ...the 4 PCB retaining screws 8 Fit new PCB refit in reverse order and refer to Replacement PCB Instructions 9 Check the operation of the boiler Refer to Section 2 33 3 18 REMOVAL OF MAIN PCB 1 Refer to...

Страница 60: ...the spare PCB to your wrist and to a suitable earthed metal 5 The System Manager is fitted beneath the main PCB To access follow points 5 7 in Section 3 18 6 With access to the System Manager remove...

Страница 61: ...SIb Return Return Flow Flow X11 Thermistors Flue Flue Heat Ex Heat Ex 0 10V 1 OpenTherm 0 10V CAN 5V CAN GND CAN 24V GV Chassis PE C Chassis PE NO PE C NO PE CH1 Boiler System CH2 DHW Shunt Valve Pum...

Страница 62: ...CAN Bus CAN VCCon CAN Mode CAN Tx CAN Bus CAN Bus 4 2 SYSTEM MANAGER WIRING DIAGRAM 4 3 OPTIONAL VARICAN ADAPTER WIRING DIAGRAM 1 2 3 4 5 1 2 3 4 1 2 3 4 5 6 7 OpenTherm lead CC 5V CC GND CC 24V Vari...

Страница 63: ...ed and any of the faults may be selected to retrieve the fault description IDEAL Evomax 2 100kW Operation Htg With temp Flow setp 82 C Flow temp 40 4 C Fault List Fault Fault Fault Fault Description F...

Страница 64: ...YSTEM FLAME FAN HYDRAULIC ETC B Low water pressure 51 5 6 W No flame signal at start restart 52 5 7 W Flameloss during operation endless restarts Parameter endless restarts activated 53 5 7 L Flamelos...

Страница 65: ...0 and 150kW approximately 240Vac for 100 and 120kW See note Check wiring from Gas Valve to PCB and replace if necessary otherwise replace the main PCB no yes Unplug the Gas Valve is the resistance bet...

Страница 66: ...e and then Extinguish no Check Gas Supply and rectify fault no Is the Gas Pressure available at the boiler 18mBar yes Is the following voltage available at the Gas Valve approximately 215Vdc for 30 40...

Страница 67: ...iring connections no Does the wiring from the Fan to the PCB have secure connections at both ends and has not deteriorated Does the wiring have continuity yes Replace main PCB Replace Fan no yes Is th...

Страница 68: ...e main PCB Change menu setting for DHW Sensor to Switched Live no Is a DHW Thermistor connected to the boiler yes Securely connect the wiring at both the boiler and cylinder thermistor no Is the wirin...

Страница 69: ...for the pump depending on the configuraiton 1 230V supply from isolate or boiler MFR 2 Volts free enable from MFR 3 0 10V signal from boiler 0 10V output Rectify fault as required Set for day or in a...

Страница 70: ...the pump depending on the configuraiton 1 230V supply from isolate or boiler MFR 2 Volts free enable from MFR 3 0 10V signal from boiler 0 10V output Rectify fault as required There is no voltage fro...

Страница 71: ...the Fuse on the combination manager PCB OK yes yes Replace combination manager PCB no Replace the system manager PCB still no display 5 17 0 10V INTERFACE Configure the boiler to accept a 0 10V input...

Страница 72: ...at have not been clearly authorised by ourselves Failure to do so could affect safety or performance of this appliance When calling and to ensure we can provide you with the most accurate parts inform...

Страница 73: ...BEEN FITTED BY PERSONS OTHER THAN THE BOILER INSTALLER visually check the integrity of the whole flue system to confirm that all components are correctly assembled fixed and supported Check that maxim...

Страница 74: ...ck that flue and flue terminal are not obstructed Check that no seals e g Those on flue extensions have been displaced during installation Rectify if necessary Turn off appliance and call Ideal Techni...

Страница 75: ...75 Installation Servicing NOTES...

Страница 76: ...76 Installation Servicing NOTES...

Страница 77: ...77 Installation Servicing NOTES...

Страница 78: ...78 Installation Servicing NOTES...

Страница 79: ...79 Installation Servicing NOTES...

Страница 80: ...Ideal Boilers Registered Office Ideal Boilers Ltd PO Box 103 National Avenue Kingston Upon Hull HU5 4JN Tel 01482 492251 Fax 01482 448858 Registration No London 322 137 Ideal Technical Helpline 01482...

Отзывы: