background image

17

SECTION 3 - SERVICING

3  SERVICING

3.1  SERVICING SCHEDULE

F

or the very latest copy of literature for specification, maintenance practices and parts replacement, visit our website                    

www.morcoproducts.co.uk where you will be able to download the relevant information. 

WARNING.

  Always turn OFF 

the gas supply at the gas service cock, and switch OFF and disconnect the electricity 

supply to the appliance before servicing.
Combustion testing must be carried out by a competent person using a combustion analyser conforming to BS7927.

To ensure the continued safe and efficient operation of the appliance it is recommended that it is checked at regular intervals and 

serviced as necessary.  The frequency of servicing will depend upon the installation condition and usage but should be carried 

out at least annually.  
It is the law that any service work must be carried out by a 

Gas Safe Registered Engineer, or in other countries a qualified and 

competent Gas Installer.

INSPECTION

1.

  Light the boiler and carry out a pre-service check, noting 

any operational faults.

2.

 Check the flue terminal (and terminal guard if fitted) is 

undamaged and clear of any obstruction.

3.

 Check all water and gas joints for signs of leakage.  

Remake any suspect joints ensuring a gas tightness 

check is carried out if applicable and the water system is 

correctly refilled, vented and re-pressurised.

CLEANING PROCEDURE

Note. 

In order to carry out either servicing or replacement of 

components the boiler upper and lower front panels 

must be removed. Refer to Section 3.2.

1.

  Clean the main burner. Refer to Section 3.4.

2.

  Clean the heat exchanger & condensate trap/siphon. 

Refer to Sections 3.5 & 3.6.

3.

  Check the main injector for blockage or damage. Refer to  

Section 3.10.

4. 

Check that the flue terminal is unobstructed and that the 

flue system is sealed correctly.

ALSO IF THE DHW FLOW RATE IS IN QUESTION :-

5.

  Check the DHW filter for blockage. Refer to Section 3.28.

The cleaning procedures are covered more fully in Sections 

3.3-3.7 and MUST be carried out in sequence.

IMPORTANT.
6.

  After completing the servicing or exchange of components 

always ensure all gas valve connections are gas tight with 

a gas soundness check up to the gas control valve.

7.

  When work is complete the front panels MUST be 

correctly refitted, ensuring that a good seal is made.

Do NOT OPERATE the boiler if the upper front 

panel is not fitted.

8.

  If, for any reason, the condensate trap/siphon has been 

removed ensure the trap is refilled with water before 

 

reassembling.

9.

  Check the gas consumption if on metered installations.

10. 

Check combustion by connecting the flue gas analyser to 

the flue gas sampling point as shown in the diagram and 

measure CO & CO

2

.

  If the CO/CO

ratio is greater than 0.004 AND the integrity 

of the complete flue system and combustion circuit seals 

have been verified and the inlet gas pressure have been 

verified, then contact Morco.

Flue Sampling Point

Air Sample

Point

Ensure all caps and seals

are re-fitted after use

GENERAL

Please Note

: During routine servicing, and after any 

maintenance or change of part of the combustion circuit, the 

following must be checked:

-  The integrity of the flue system and the flue seals,

-  The integrity of the boiler combustion circuit and the 

relevant seals

-  The operational (working) gas inlet pressure at maximum 

rate.  Turn on one or more DHW taps

-  The combustion performance.

COMPETENCE TO CARRY OUT THE CHECK OF 

COMBUSTION PERFORMANCE

Please Note

BS 6798:2009 Specification for installation 

and maintenance of gas-fired boilers of rated input not 

exceeding 70kW net advises that:
-  The person carrying out a combustion measurement 

should have been assessed as competent in the use of a 

flue gas analyser and the interpretation of the results.

-  The flue gas analyser used should be one meeting 

the requirements of BS7927 or BS-EN50379-3 and be 

calibrated in accordance with the analyser manufacturers 

requirements.

SERVICE MODE

To access the service mode:
Press and hold the restart and function button for 5 seconds.  

The display will show the last 3 fauls followed by “

S H

”.

Содержание III Series

Страница 1: ...co uk To Domestic Hot Water GB24 Propane Minimum 4 9 kW 16 600 Btu h GB30 Propane Minimum 6 1 kW 20 700 Btu h GB24 Propane Maximum 24 2 kW 82 570 Btu h GB30 Propane Maximum 30 3 kW 103 384 Btu h To C...

Страница 2: ...2 Combination Boiler Destination Country GB UK IE Ireland Ideal GB24 GB30 Series III...

Страница 3: ...rk Generator Replacement 23 3 14 Gas Control Valve Replacement 24 3 15 Divterter Valve Actuator Replacement 24 3 16 Condensate Trap Siphon Replacement 25 3 17 Main PCB Replacement 26 3 18 Replacing Th...

Страница 4: ...rformance Data Domestic Hot Water Required for maximum flow rate Boiler operates down to 2 l min DHW delivery Ideal GB Series III 24 30 Gas Supply I3P G31 37mbar Gas Supply Connection 15mm copper comp...

Страница 5: ...draw off of 24 9 9 l min at 35 o C temperature rise 30 12 4 l min at 35 o C temperature rise The DHW draw off rate specified above is the nominal that the boiler flow regulator will give Due to system...

Страница 6: ...Gas Installer In the approved country the boiler is installed this must be in accordance with their current rules in force Detailed recommendations are contained in the following British Standard Code...

Страница 7: ...e length of flue required the flue must be fitted from the outside Installation from inside ONLY b If a core boring tool or hole cutter is to be used inside the dwelling the space in which the boiler...

Страница 8: ...CTOR ASSEMBLY 214 VENTURI 215 FAN 217 BURNER 218 GASKET BURNER 219 SUMP CLEAN OUT COVER 223 FLUE MANIFOLD 224 FLUE MANIFOLD TOP 227 CLAMP RETAINING FLUE TURRET 228 HOSE CONDENSATE INTERNAL 229 SIPHON...

Страница 9: ...e air duct MUST be sealed with sealant to create an adequate seal WALL Aluminium Flue Collar RSF 060 Fill with sealant 17mm min Internal Sealing Flubber Fill with sealant It is IMPORTANT that all atta...

Страница 10: ...outer edge to aid assembly Centre of turret to edge of turret 100mm Turret has a flue insertion of 30mm The white outer flue tube must protrude the wall by 17mm From centreline of turret to wall Rear...

Страница 11: ...turret on until it has travelled 30mm on to the flue pipe and is fully engaged Make sure the flue has not rotated or moved forward during fitting and the flue seam is upper most 3 Push the turret into...

Страница 12: ...e boiler and its flue system Note The resistance of the deflector is equivalent to 1 metre of flue length Ensure this is used when calculating the maximum allowable flue length 2 Choose the direction...

Страница 13: ...alcony 500 mm Below velux windows 2000mm Above or side of velux windows 600mm 2 9 ASSEMBLING THE ROOF FLUE KIT 1 Position the roof plate supplied separately over the hole cut in the roof and insert fl...

Страница 14: ...nating into a suitable internal foul water discharge point such as an internal soil and vent stack or internal kitchen or bathroom waste pipe etc fig 3 External Drain Connections The use of an externa...

Страница 15: ...ater Weather proof insulation Max 3m external pipework Limestone chippings 500 300 25 2 rows of three 12mm holes 25mm centres 50mm from the bottom of the tube facing away from the house Minimum connec...

Страница 16: ...E DHW LIVE X3 PUMP GND X9 X8 OWC OWC OPENTHERM OPENTHERM CHIP COM BUS TX CHIP COM BUS 24V CHIP COM BUS GND CHIP COM BUS 5V CHIP COM BUS RX MAINS LIVE MAINS NEUTRAL AUXILIARY LIVE IONISATION FLOW DHW D...

Страница 17: ...leaning procedures are covered more fully in Sections 3 3 3 7 and MUST be carried out in sequence IMPORTANT 6 After completing the servicing or exchange of components always ensure all gas valve conne...

Страница 18: ...onto the top retaining clips 5 Retain the upper panel with the two fixing screws previously removed ensuring a good seal is made 6 Swing the lower front panel up and retain with the two screws 7 Close...

Страница 19: ...er head is a ceramic plaque construction Care must be taken to ensure that the burner is not placed down upon its face as this may cause damage to the ceramic 6 Brush off any deposits that may be on t...

Страница 20: ...nition gap is correct Refer to Sections 3 12 3 13 1 Ignition Electrode Earth Wire Reassemble the boiler in the following order 1 Ensure that the condensate trap siphon is full of water 2 Refit the bur...

Страница 21: ...to Section 3 19 THE BOILER MUST NOT BE OPERATED WITHOUT THE FRONT PANEL FITTED 3 9 FAN REPLACEMENT 1 Refer to Section 3 8 2 Disconnect the electrical leads from the fan 3 Remove the clip from the gas...

Страница 22: ...any damaged or deteriorating sealing gasket 8 Reassemble in reverse order 9 Check the operation of the boiler 1 Refer to Section 3 8 2 Disconnect the electrical leads from the fan 3 Remove the clip fr...

Страница 23: ...the electrode 7 Fit the new ignition electrode using the new gasket supplied Check dimensions as shown 8 Reassemble in reverse order 9 Check the operation of the boiler Ignition Electrode 3mm Straigh...

Страница 24: ...ATOR REPLACEMENT Refer to Section 3 8 To remove the motor 1 Remove the condensate trap siphon Refer to Section 3 16 2 Place a flat bladed screwdriver in the actuator slot provided and ease out the act...

Страница 25: ...off the rubber pipe at the siphon 3 Turn the siphon clockwise to disengage and lift to remove 4 Reassemble in reverse order 5 When reassembling ensure the trap is full of water 6 Check operation of t...

Страница 26: ...uide and secure this to the new PCB 9 Insert the new PCB and secure all electrical connections Ensure control knobs are correctly aligned with PCB 10 Reassemble in reverse order If programming of the...

Страница 27: ...ill be experienced during replacement of components 3 After replacing any component on the boiler DHW circuit re fill as appropriate 4 Check operation of the boiler CENTRAL HEATING CIRCUIT 1 Refer to...

Страница 28: ...reeze Check operation of the boiler 5 7 4 1 Refer to Section 3 8 2 Drain the heating system Refer to Section 3 19 3 Remove the boiler front See Section 3 8 lower the control panel and remove the contr...

Страница 29: ...7 Remove the pump electrical connection Refer to Section 3 26 no 3 8 Remove DHW Turbine electrical connection Refer to Section 3 20 no 3 9 Remove the DHW plate heat exchanger note orientation Refer to...

Страница 30: ...g a suitable tool pull out the metal retaining clip 5 Carefully withdraw the pressure switch 6 Fit the new pressure switch and re assemble in reverse order 7 Refill the boiler and add the correct volu...

Страница 31: ...anner should be used 5 Fit the new thermistor using the sealing washer provided 6 Reassemble in the reverse order 7 Refill the boiler and add the correct volume of anti freeze 8 Check the operation of...

Страница 32: ...llows clearance of the pipe from heat exchanger plugs Lift pipe and remove 13 Remove the two heat exchanger fixing screws 14 To remove the Heat exchanger slide out of location bracket 15 Remove the co...

Страница 33: ...pressure to 0 75 bar 5 Re assemble in reverse order re fill the boiler and add the correct volume of anti freeze 6 Check operation of the boiler REPLACEMENT 7 Refer to Section 3 8 8 Drain the boiler C...

Страница 34: ...r hot water but the appliance has reached the desired temperature set on the boiler The boiler is operating in central heating mode The boiler is operating in domestic hot water mode The boiler is ope...

Страница 35: ...er letter refer to page 34 L Boiler is in lockout for a specific error Display will show L with a number or letter to show which error is detected F Boiler has a fault for a specific error Display wil...

Страница 36: ...e house are working to confirm a supply is present in the property 3 If other appliances do not work or there are no other appliances check the gas supply is on at the meter and or pre payment meter h...

Страница 37: ...FAULT GO TO SECTION 4 13 RETURN THERMISTOR FAULT GO TO SECTION 4 14 OUTSIDE SENSOR FAULT LOW MAINS VOLTAGE CONTACT ELECTRICITY PROVIDER NEGATIVE DIFFERENTIAL FLOW OR RETURN THERMISTOR FAULT PCB UNCONF...

Страница 38: ...Check wiring connection from gas valve to PCB for continuity If the wiring is OK then replace the PCB NO Replace Spark Generator and harness as necessary NO Replace ignition detection electrode and a...

Страница 39: ...Are the Boiler and CH System filled with water and radiator valves open check pressure gauge is between 1 to 1 5 bar NO NO YES Fill and vent the system and open all isolation valves YES Are connection...

Страница 40: ...lectrode and associated harness for continuity visual condition and position Refer to Section 3 12 Are these functioning correctly YES Check siphon and condensate drain pipe work for blockage and rect...

Страница 41: ...NO Securely connect the wiring to the PCB Is the wiring securely connected to the Flow Thermistor located in the top of the Heat Exchanger YES NO Securely connect the wiring to the Flow Thermistor NO...

Страница 42: ...Disconnect the wires to the outside sensor Check the resistance using a suitable multimeter connected across the Outside Sensor s terminal pins At 0 o C expect 31 000 35 000 Ohms At 15 o C expect 15...

Страница 43: ...rise and check filter fitted in turbine is not blocked with debris NO Reconnect wiring or replace wiring harness if no continuity NO Re engage diverter head NO Replace PCB Is hot and cold pipework cr...

Страница 44: ...spare parts product training please phone us on 01482 325456 or contact us at the address below MORCO PRODUCTS LTD Morco House Riverview Road Beverley East Yorkshire HU17 0LD TEL 01482 325456 FAX 014...

Отзывы: