25
icos
-
Installation & Servicing
INSTALLATION
FLUE OUTLET
32 ASSEMBLING THE ROOF FLUE KIT
Determine the correct height that the flue should terminate
above the roof. If after calculating or measuring the overall flue
height from the top of the boiler, it is necessary to cut both
pipes of assembly A, then ensure they are cut equally leaving
the inner flue tube 20mm longer than the outer air tube as
supplied. (Refer to No. 5 below)
Ensure the cut pipe ends are free from any burrs.
1.
Ensure the flue seal collar B is located onto the flue
assembly A.
2.
Position the roof flashing plate D (supplied separately) over
the hole cut in the roof and insert flue assembly A from the
roof end.
3.
Fit the sealing gasket and push fit the vertical connector E
(supplied separately) into the boiler flue connection and
retain with the four securing screws provided. Lubricate flue
seal using lubricant (supplied in hardware pack).
4.
"Push" fit extension duct F (if required, supplied separately)
and the roof flue kit assembly A into the vertical connector E.
Lubricate seals using lubricant (supplied in hardware pack).
5.
If the last extension duct requires cutting, measure the
distance (outer ducts) between the duct and the
terminal and add 100 mm to this dimension. This
gives the length of the last extension duct.
Note.
Check the position of the inner flue duct
relative to the outer duct on the assembled
extension duct(s) and ensure the terminal flue
duct is cut 20mm longer than the air duct to
ensure engagement in the final flue duct seal.
6.
Slide down and position the flue seal collar B
over the roof plate D and secure it with the 3
screws C to the flue assembly A.
7.
Finally ensure the roof flashing plate D is
correctly sealed to the roof.
A
B
7469
1
ix7474
A
C
B
A
C
B
D
6
E
3
nm8168
min 16
o
max 41
o
MAX LENGTH:
HE 30 - 5m
HE 36 - 5m
7470
A
D
A
D
2
nm8170
4
F
E
5
nm8256
202414-6.pmd
19/02/2008, 13:07