19
icos
-
Installation & Servicing
INSTALLATION
FLUE OUTLET
1.
A
maximum
of 3 extension ducts (one suitably
cut) plus the standard flue duct may be used
together.
2.
Flue extensions of greater length than 1m (39")
should be supported with the bracket provided,
suitably adjusted.
21 FLUE EXTENSION DUCTS - continued
Ecl 6085
Boiler
Standard flue
Terminal grille
Flue length
Extension flue
1.
Fit the inner flue extension duct onto the inner flue duct.
2.
Fit the outer flue extension duct onto the outer air duct.
3.
Using the clamp provided, clamp the flue lengths together.
4.
Repeat steps 1-4 if a second flue extension is required.
22 FITTING THE KIT
20 FLUE EXTENSION DUCTS - For flue lengths greater than 775mm
Pack D Flue extension duct kit contents.
Note.
Side flue shown
Use a maximum of 3m extended flue ONLY
General arrangement
Flue duct support
Wall plugs - 2 off
Extension duct
1.0m (39") long
Support fixing screws - 2 off
Clamp screws - 2 off
nm8242
Washers - 2 off
Measure from
this
RING
1
2
mxhe7843
5.
Measure and mark the flue length required onto the flue,
measuring from the ring near the terminal.
6.
To ensure a square cut, mark the flue all the way around.
7.
Cut to length, and deburr the metal edges.
202414-6.pmd
19/02/2008, 13:07
19