Installation Manual | April 2011
The settings which can be programmed via the DIP switches are shown in the following table.
Switch
Variable
Setting
Action
1-2
Temperature Set Point
1 2
ON
OFF
22˚C (71.6˚F)
1 2
ON
OFF
4˚C (39.2˚F)
1 2
ON
OFF
10˚C (50.0˚F)
1 2
ON
OFF
26˚C (78.8˚F)
3-4
Humidity Set Point
3 4
ON
OFF
60%
3 4
ON
OFF
40%
3 4
ON
OFF
50%
3 4
ON
OFF
70%
5
Alarm Mode
5
ON
OFF
Alarm Above
5
ON
OFF
Alarm below
6
Invert Outputs
6
ON
OFF
None
6
ON
OFF
Invert
7-8
Mode Setting
7 8
ON
OFF
Protege Mode
7 8
ON
OFF
Standalone Mode using Serial Port Settings
7 8
ON
OFF
Standalone Mode using DIP Switch Settings