10
PRT-ATH1 / ACC-ATH1
Protege Temperature and Humidity Sensor
Installation Manual | April 2011
4.3
Thermocouple Wiring
While the internal temperature sensor may be suitable for most applications, the Protege Temperature and
Humidity Sensor can also be used with an external thermocouple.
A K-Type thermocouple must be used and
should be connected as shown in the diagram below. Note that, of the four pins of the connector, the two left
hand pins are internally connected together, and the two right hand pins are internally connected together.
-
White
+
Green
Connecting a K-Type Thermocouple