The e-mail settings on the
Network Setup
page must be configured
correctly before any e-mail notifications can be sent.
DC OUTPUT FAILURE ALARM
The alarm latches the output off, and clears when the DC output is
manually re-enabled.
Activate Alarm Form C Contact:
If this box is checked, the
ate a
fault condition when the Output Voltage or current rises
above approximately 110% of the max-rated output.
Send E-mail:
If this box is checked, an e-mail alarm
notification will be sent when a DC output failure occurs.
AC INPUT FAILURE/SYSTEM FAILURE ALARM
The alarm latches the output off when the AC voltage fails, and
automatically clears when the AC input voltage rises above
approximately 100Vac for 3 seconds, and any internal fault is
resolved.
Activate Alarm Form C Contact:
If this box is checked, the
fault condition when the AC input voltage falls below
approximately 90Vac, or there is an internal power supply
fault. (Note: The form C contact will be activated any time the
unit completely loses AC power, regardless of this setting.)
Send E-mail:
If this box is checked, an e-mail alarm
notification will be sent when the AC input is out of range.
OVER-TEMPERATURE ALARM
The alarm latches the output off, and automatically clears when the
internal temperature falls to within a normal operating range.
Activate Alarm Form C Contact:
If this box is checked, the
fault condition when an internal or battery over-temperature
limit is exceeded.