Innovative Circuit Technology Ltd.
25
4.5. Changing a Power Supply Back To a Standalone
Unit
To release a unit from parallel operation and change it back to a
Standalone unit, do the following:
1.
Turn the Power Switch on all parallel units to the OFF position.
2.
Disconnect the connections to the positive terminal (labeled
SHARE interface
).
3.
4.
In the front Control Panel menu, scroll to the Parallel Settings
screen and press Enter.
5.
Scroll to the Parallel Mode setting and press Enter. Scroll and
choose Standalone as the parallel mode setting, then press
Enter.
6.
The unit is now configured as a Standalone unit. If the unit was
previously configured as a Slave unit, the System Settings
Control Panel screen will now be unlocked. Note that when the
Parallel Mode setting (Standalone/Master/Slave) is changed to a
different setting on a unit, the DC Output of that power supply will
automatically be turned OFF if it is currently enabled. You will
need to verify the output voltage/current settings, and then
manually enable the output.
5. TCP/IP WEB BASED UTILITY OPTION
Use the embedded Web server via an Ethernet connection to monitor
the status of the power supply, and change the power supp
settings and configuration when the unit is powered from the AC line
or an external back-up battery.
The embedded Web server provides a full featured interface to the
power supply that can be easily accessed through a standard Web
browser on any network-connected computer. There is no additional
software to install or configure.