View Device Name:
Default is ICT DIGITAL SERIES . The device
name can only be changed on the Ethernet GUI network page.
Reset Comm Settings:
Resets the Web server Administrator
password, IP address, and port settings to the original factory default
values. See the Administrator Password / IP Address Reset section for
more information.
BATTERY SETTINGS SCREEN
BATTERY SETTINGS
LVD SETTINGS
CONFIGURE BATTERY
EQUALIZE CHARGE
The Battery Settings screen is available when the Battery Backup
These settings allow you to adjust the battery
Low Voltage Disconnect (LVD) points, configure the battery
maximum charge current, float voltage temperature compensation,
and Equalize charge settings.
The Equalize Charge can be used on flooded lead-acid batteries to
apply a higher than normal charge voltage to a fully charged battery
for a limited time to help force all cells to the same state of charge,
and prevent stratification of the electrolyte in each cell.
WARNING!
Potential for personal injury, or damage to property and
equipment due to overcharging of the external battery!
Use Equalize charge on flooded lead-acid batteries only. Do not
use this feature on any type of sealed battery.
Do not exceed the Equalize voltage setting recommended by the
battery manufacturer