background image

6.  To access the panel over the Internet, type the WAN IP Address of the router in the 
location/address field of your browser, followed by a colon and the HTTP port number that the panel 
is using (e.g. 

http://209.123.10.33:8000

 for IP Address 

209.123.10.33

, Port 

8000

).

Figure 10.

26

Figure 9.

Содержание ICT180S-12IRC

Страница 1: ...0 0 90 065 7 5 3 ICT180S 12IRC INTELLIGENT MODEL 0 5 5 6 0 0 9 0 5 6 3 6 3 INSTRUCTION MANUAL WITH REMOTE POWER CONTROL SERIES 2 The Power of Reliability www airadio com Distributed by ...

Страница 2: ......

Страница 3: ...us Control Page 10 Device Setup Page 11 Output Setup Page 13 Network Setup Page 16 E mail Setup Page 18 Alarm Setup Page 19 User Setup Page 21 Maintenance Page 22 Mobile Web App Page 23 Password Reset Page 24 Router Configuration Page 24 Text Message Alarm Notifications Page 27 Troubleshooting Page 28 Product Specifications Page 29 Limited Warranty Page 30 1 ...

Страница 4: ...before installing or removing fuses or connecting or disconnecting wiring Use wire and connectors rated for the maximum load current and size of fuse or circuit breaker Carefully observe wiring polarity when making input and output connections Securely tighten all connections and insert fuses fully No internal user serviceable parts Refer all product service to an authorized ICT Ltd service facili...

Страница 5: ... circuit for monitoring alarms generated by the panel Remote monitoring is available through the integrated security protected Ethernet communications port on the back of the panel The panel has a built in web server with an embedded web based GUI that can be accessed using any standard commercial web browser such as Internet Explorer The web server not only displays panel information it can also ...

Страница 6: ...spect panel and accessories to make sure everything is complete and in good condition 2 For rack set up install panel on the rack using appropriate size screws and star washers on all four mounting holes If equipment rack is not electrically connected to Earth ground connect a ground cable from the ground stud on the back of the panel to a known Earth ground point Otherwise the four mounting screw...

Страница 7: ...control connect your network interface to the Ethernet port on the back of the panel The recommended cable for Ethernet connection is Cat5e UTP network cable 8 The Alarm Form C Contacts on the back of the panel can be connected to an external alarm circuit to monitor alarms generated by the panel Depending on the alarm circuit refer to table 2 connect it between normally open NO and common C betwe...

Страница 8: ...is checked and no fault occurred System Over Voltage Alarm System Over Current Alarm All Activate Alarm Form C Contact is not checked No power to unit Alarm Input 1 5 Activate Alarm Form C Contact is checked Digital Alarm is triggered Output Over Current Alarm 1 12 Activate Alarm Form C Contact is checked Output Current is above the set value Output Under Current Alarm 1 12 Activate Alarm Form C C...

Страница 9: ...for screen order Figure 3 LCD Screens 7 Holding the Output Select button for 2 seconds at any screens will return you to the main screen Holding the Output Select button for 20 seconds at any screens will reset the password see Password Reset section The backlight of the LCD turns off if the Output Select button is not pressed for 15 minutes Press the Output Select button to turn the backlight bac...

Страница 10: ...ine 2 Displays the output status ENABLED for output enabled DISABLED for output disabled and FUSE OPEN for blown or missing fuse Line 3 Displays the output voltage Voltage display will blink if the voltage exceeds the Under Voltage or Over Voltage Thresholds set on the Alarm Setup page Line 4 Displays the output current for that individual output Current display will blink if the output current ex...

Страница 11: ...address field of the browser If the panel is connected to a network with a DHCP server the panel will be assigned an IP address automatically To find the current IP address of the panel see the LCD Operation section in the instruction manual If the panel is not connected to a network with DHCP it will use a default IP address of 192 168 0 180 3 Enter your user name and password The default Adminis...

Страница 12: ...ts will be shown on this page If an alarm input number is displayed in a grey box the alarm sensor is ready If an alarm input number is displayed in a red box the alarm sensor is in an alarm condition Enable All Outputs Pressing this button will enable DC power to all outputs If power on sequencing is enabled on the Device Setup page the outputs will be enabled in sequence instead of enabling them...

Страница 13: ...Server A valid server address must also be entered in the NTP Server field NTP Server The name or IP address of the NTP Server used for date and time synchronization such as pool ntp org Time Zone Select a time zone to convert the time received from the NTP Server to your local time Set Time Manually Checking this box will allow you to manually set the panel s date and time The date must be entere...

Страница 14: ...page Secondary IP Address An optional second remote IP address can be entered in this field If entered the Network Watchdog will only trigger if both the Primary and Secondary IP Addresses fail to respond Watchdog Timeout Enter the time duration in minutes that the remote IP addresses must stop responding to Ping requests before the Network Watchdog will trigger and power cycle outputs The default...

Страница 15: ...ame state after the panel starts up Enable Output If this option is selected this output will always be enabled after the panel starts up after a power failure or reset Disable Output If this option is selected this output will always be disabled after the panel starts up after a power failure or reset Ignore Fuse Status If this box is checked the panel will not monitor the status of the fuse for ...

Страница 16: ... is unchecked outputs will need to be manually re enabled after load shedding is triggered Auto Recovery Threshold Enter the load shedding recovery voltage for the selected output The value in this field must be at least 0 50V higher than the load shedding threshold voltage OUTPUT OVER CURRENT ALARM Over Current Threshold If the current on the selected output rises above the value in this field th...

Страница 17: ...le this alarm set the value in this field to 0 Amps Activate Alarm Form C Contact If this box is checked the Alarm Form C Contacts on the panel will indicate a fault condition when the under current alarm is triggered for the selected output Send E mail If this box is checked an e mail alarm notification will be sent when the under current alarm is triggered for the selected output The e mail sett...

Страница 18: ...ary DNS Server for your network Secondary DNS Specify the IP address of the Secondary DNS Server for your network WEB SERVER WARNING Changing these ports may affect your ability to access the panel The web server port numbers can be changed to any port within the range 1 65565 HTTP Port Allows you to change the HTTP port number This port is used for HTTP traffic between the panel and web browser T...

Страница 19: ...ssword here for read only SNMP access The default read community string is public Trap Community Enter the community string password that is sent with all traps Some trap receivers are able to filter on trap community Trap IP Addresses Enter the IP addresses for up to two devices that will receive SNMP traps from the panel Enable SNMP Write Access Turning on this setting will allow you enable or d...

Страница 20: ...rver requires a user name and password enter the user name here Leave this field blank if your SMTP server does not require authentication SMTP Password If your SMTP server requires a user name and password enter the password here Leave this field blank if your SMTP server does not require authentication Minimum E mail Interval This setting allows you to specify how many minutes have to elapse bet...

Страница 21: ...ge alarm will clear The value in this field must be at least 0 50V higher then the Under Voltage Threshold Activate Alarm Form C Contact If this box is checked the Alarm Form C Contacts on the panel will indicate a fault condition when the system under voltage alarm is triggered Send E mail If this box is checked an e mail alarm notification will be sent when the system under voltage alarm is trig...

Страница 22: ...p page must be configured correctly before e mail notifications can be sent ALARM INPUT 1 5 Alarm Name Allows you to assign a custom name to each individual alarm input Contact Type Allows you to configure each individual alarm input as a Normally Open contact a Normally Closed contact or as Not Used If the alarm input is configured as Not Used it will be disabled and will not appear on the Status...

Страница 23: ...ssword to the default setting See the Password Reset section for more information Select a User to Edit There are two user accounts with access to the panel Administrator user name admin This account has full access to the panel Standard User user name user This account has view only access to the panel This account cannot be used to enable disable outputs or change settings New Password Allows yo...

Страница 24: ...the reset RESTORE FACTORY DEFAULT SETTINGS Pressing the Restore button will restore ALL settings to the original factory default values including the passwords If you only want to restore the network settings and passwords see the Password Reset section SEND TEST E MAIL Pressing the Send Test E mail button will send test e mail to the specified recipient using the e mail settings on the Network Se...

Страница 25: ...ng a HTTPS connection or use a Virtual Private Network VPN connection Figure 7 Mobile Web App The Mobile Web App provides information on system voltage system current alarm input status output status and current level by output contact 1 through 12 If you are logged in using the Administrator account you can enable or disable DC power to individual outputs by tapping on the output cells Tap the En...

Страница 26: ...rding screen In the Linksys WRT54G this is located in the Applications and Gaming tab The location of port forwarding may be different on other routers consult your router manual for instructions 2 To configure HTTP forwarding following these steps a Enter a unique name in the Application field b Enter the HTTP port number that the panel is using in the Start and End fields If you are using the de...

Страница 27: ...peat steps 2a 2e with the HTTPS port number that the panel is using If you are using the default panel port settings the HTTPS port number is 443 4 To set up your router to allow remote panel firmware upgrades repeat steps 2a 2e with the UDP port number that the panel is using If you are using the default panel port settings the UDP port number is 9393 Firmware upgrades can still be applied locall...

Страница 28: ...type the WAN IP Address of the router in the location address field of your browser followed by a colon and the HTTP port number that the panel is using e g http 209 123 10 33 8000 for IP Address 209 123 10 33 Port 8000 Figure 10 26 Figure 9 ...

Страница 29: ...field For example to send a text message to an AT T phone enter cellnumber txt att net replacing cellnumber with your cell phone number Here are some address formats for other mobile phone providers AT T cellnumber txt att net Verizon cellnumber vtext com T Mobile cellnumber tmomail net Virgin Mobile cellnumber vmobl com Nextel cellnumber messaging nextel com Bell Mobility cellnumber txt bell ca R...

Страница 30: ...the URL used to access the panel See the Password Reset section for instructions on how to reset the port number to the default setting If your network switch allows you to manually configure port speed and duplex settings turn on Auto negotiation on the switch port that the panel is connected to I forgot my password See the Password Reset section for instructions on how to reset the password I am...

Страница 31: ... Cable Length 100 meters Voltage Drop without fuse 60mV Typical Alarm Form C Contact Form C Dry Contacts 1A 60VDC Max Alarm Sensor Inputs External dry contact alarm inputs configurable for NO or NC logic Applied voltage 3 3V 0 4mA for contact closure detection Ethernet RJ45 10Base T 100Base T SNMP SMNPv1 v2c Input Connector Heavy Duty Insulated M10 Stud 75in lbs Max Output Connector Barrier Termin...

Страница 32: ...ials accurately describe ICT product specifications and capabilities at the time of publication However because of ongoing improvements and updating of ICT products ICT cannot guarantee the accuracy of printed materials after the date of publication and disclaims liability for changes errors or omissions If this ICT product is not in good working order as outlined in the above warranty your sole r...

Отзывы: