PRODUCT DESCRIPTION
The
ICT180-12IRC
Intelligent Distribution Panel with Remote Power Control is designed for either 12
or 24VDC applications. It provides 12 output positions that are individually protected by blade type
fuses. Nine of the outputs use the ATO/ATC blade fuse that are rated up to 25A each. Three of the
outputs use the MAXI blade fuse and are rated up to 40A each. These fuses are located on the front of
the panel for easy monitoring and replacement. Each positive output terminal point is connected
through a fuse to a positive internal bus. All negative output terminal points are connected to a
negative internal bus.
System voltage, system current, output currents and fuse status can be monitored onsite through the
LCD graphics display. Fuse status is also displayed by an LED indicator. Form “C” alarm contacts
(C/NO/NC) are provided on the back of the panel for an external alarm circuit.
Remote monitoring is available through the integrated security protected Ethernet communications
port on the back of the panel. The panel has a built-in web server with an embedded web-based GUI
that can be accessed using any standard commercial web browser such as Internet Explorer. The web
server not only displays panel information, it can also be set up to send an alarm to a user-defined
email account in the event a fault occurs. The web server can also be for data logging of up to 30
hours of event information. All these features are packaged in a 1RU enclosure to save valuable rack
space, with a 19” wide front plate to fit standard 19” equipment racks.
DC outputs can be turned on and off remotely, allowing connected loads to be power-cycled through
the Ethernet connection.
FRONT PANEL
Figure 1.
1. FUSE STATUS LEDs: Turns on when a fuse is blown or missing.
2. ATO/ATC FUSES: Location of the ATO/ATC fuses rated up to 25A.
3. LCD: Displays system voltage, system current, output current and fuse
status for each of the 12 output positions.
4. SELECT BUTTON: For switching between LCD screens, and resetting network,
web server and password settings to original factory default values.
5. MAXI FUSES: Location of the MAXI fuses rated up to 40A.