PRODUCT SPECIFICATIONS
Operating Voltage:
10 to 30VDC
Panel Capacity:
150A (Continuous)
180A
(Peak)
Fuse Capacity:
25A Maximum ATO/ATC Blade x 9
40A Maximum MAXI Blade x 3
Note 1: Ensure that the load total connected to the fused outputs does not exceed the panel capacity rating.
Note 2: Most fuses should be continuously operated at no more than 80% of their nominal current rating.
Consult the fuse manufacturers specifications.
Power Consumption:
2.5 watts
Maximum Cable Length:
100 meters
Voltage Drop (without fuse): 60mV (Typical)
Alarm Contact:
Form “C” Dry Contacts
1A/60VDC
Max
Ethernet:
RJ45,
10Base-T
Input Connector:
Heavy Duty Insulated M10 Stud
75in-lbs
Max
Output Connector:
Barrier Terminal Block
M4
Screws
8
–
20AWG
Wire
Range
12in-lbs
Max
Alarm Connector:
Euro Terminal Block
M2
Screws
16 – 28AWG Wire Range
1in-lbs
Max
Operating Temperature:
-4°F to 140°F
-20°C
to
+60°C
Dimensions:
19.0” x 9.29” x 1.75”
483mm x 236mm x 45mm
Weight:
8.0lbs
3.6kg
Warranty:
3
years
21