Tunnel Master® Jr. User Manual
- Page 24
Chapter 3: Entrance Keypad Installation
Chapter 3: Entrance Keypad Installation
Entrance Keypad Mounting
The Entrance Keypad should be mounted securely to the wall of the car wash, in the
entrance to the tunnel, at approximately chest height.
The Entrance Keypad is a Type 3 enclosure, which means it is a watertight enclosure, but
should not be mounted where it is constantly inundated with water.
The Entrance Keypad should be mounted away from corrosive chemicals.
Entrance Keypad Wiring
Locate conduit that was run from the Tunnel Master® Jr. relay box.
The conduit shall be secured with a Listed watertight conduit hub, and should be
tightened to the torque specs of the manufacturer. Over torquing may cause enclosure
breakage.
The conduit will contain the 12 VAC and Communications cable and should enter the
opening in the bottom of the keypad enclosure.
Electrician must run 3 - 18 AWG wires, or cable (supplied by the electrician) through the
3/4” conduit from the Tunnel Master Jr. to the Entrance Keypad.
The following picture shows the connection points for the various components.
Optional Pole
Display screen
termination -or-
this can also be
where an optional
printer is hooked
up as well.
Communications
wire termination
points. You can
use either terminal
block. This is where
a second keypad
would be wired as
well.
12 VAC termination block
Figure 3-1. Keypad Connectors (Keypad Board)
There is a terminal block (POWER), located on the keypad circuit board labeled with
ACH
for line,
ACN
for neutral, and
GND
for Ground. Terminations for the 3 – 18AWG wires should be torqued
to 20 pound-inches (2.3 n-m.) Over torquing may cause enclosure breakage.
The Tunnel Master Jr. is equipped with a 12 VAC transformer, which is to be used to power the
Entrance Keypad. If a second transformer is present, the 12 VAC terminations must be made as in
Figure 3-2 from the separate transformer. If there is only one transformer, terminate power from
it.
Electrician must run a single-twisted pair, 24AWG shielded COMM cable (can be purchased from
ICS) through 3/4” conduit from the 485 terminal to the Entrance Keypad.