![ICPDAS DL-100-E Скачать руководство пользователя страница 70](http://html1.mh-extra.com/html/icpdas/dl-100-e/dl-100-e_user-manual_3510612070.webp)
DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020
- 70 -
Address Description
Attribute
40486
RS-485 baud rate and parity settings
Bits 5:0
Baud rate, valid range: 3 ~ 10
Bits 7:6
00: no parity, 1 stop bit
01: no parity, 2 stop bit
10: even parity, 1 stop bit
11: odd parity , 1 stop bit
Only for Modbus RTU protocol
R/W
40488
RS-485 response delay time in ms, valid range, 0
~ 30
Only for Modbus RTU protocol
R/W
40489
RS-485 host watchdog timeout value, 0 ~ 255, in
0.1s
Only for Modbus RTU protocol
R/W
40492
RS-485 host watchdog timeout count, write 0 to
clear
Only for Modbus RTU protocol
R/W
30513 ~
30519
40513 ~
40519
High latched analog input value of channel 0 to 6 R
30545 ~
30551
40545 ~
40551
Low latched analog input value of channel 0 to 6 R
30556
40556
Module reset status, 1: power-on, 2: watchdog, 3:
software reset command
Only for Modbus TCP protocol
R
40558
Ethernet host watchdog timeout value, 5 to 65535,
in second, 0 to disable.
Only for Modbus TCP protocol
R/W
30559
40559
Ethernet host watchdog timeout count.
Only for Modbus TCP protocol
R
30560
40560
Module name, 0x0110
Only for Modbus TCP protocol
R
Содержание DL-100-E
Страница 9: ...DL 100 E DL 101 E DL 110 E DL 120 E User Manual Version 1 1 3 Dec 2020 9 2 2 Appearance...
Страница 17: ...DL 100 E DL 101 E DL 110 E DL 120 E User Manual Version 1 1 3 Dec 2020 17 2 3 Dimensions unit mm...
Страница 57: ...DL 100 E DL 101 E DL 110 E DL 120 E User Manual Version 1 1 3 Dec 2020 57...
Страница 61: ...DL 100 E DL 101 E DL 110 E DL 120 E User Manual Version 1 1 3 Dec 2020 61...