background image

20

Specifications subject to change without notice.

516 01 3604 04

Fig. 34 — Typical Low-Voltage Control Connections

CENTRAL TERMINAL BOARD
The Central Terminal Board (CTB) is a pass through con

-

nection point. The CTB provides the capability to add facto

-

ry-installed  options  and  field-installed  accessories  to  the

units by cutting jumper wires without having to change or re

-

route wires through the structure of the unit. The CTB does

not provide any microprocessor control; it is simply a basic

multifunction wiring terminal configuration.
COMMERCIAL DEFROST CONTROL
The Commercial Defrost Control Board (DFB) coordinates

thermostat  demands  for  supply  fan  control,  1  or  2  stage

cooling,  2  stage  heating,  emergency  heating  and  defrost

control with unit operating sequences. The DFB also pro

-

vides an indoor fan off delay feature (user selectable). See

Fig. 35 for board arrangement.

The DFB is located in the RHH unit’s main control box (see

Fig.  2  and  36). All  connections  are  factory-made  through

harnesses to the unit’s CTB, to IFC (belt-drive motor) or to

ECM (direct-drive motor), reversing valve solenoids and to

defrost thermostats. Refer to Table 6 for details of DFB In

-

puts and Outputs.

Fig. 35 — Defrost Control Board Arrangement

Reversing valve control

The DFB has two outputs for unit reversing valve control.

Operation of the reversing valves is based on internal logic;

this application does not use an “O” or “B” signal to deter

-

mine reversing valve position. Reversing valves are ener

-

gized during the cooling stages and the defrost cycle and

de-energized during heating cycles. Once energized at the

start of a cooling stage, the reversing valve will remain ener

-

gized until the next heating cycle demand is received. Once

de-energized at the start of a Heating cycle, the reversing

valves will remain de-energized until the next cooling stage

is initiated.

Compressor control

The  DFB  receives  inputs  indicating  Stage  1  Cooling,

Stage 2 Cooling and Stage 1 Heating from the space ther

-

mostat  or  unit  control  system;  it  generates  commands  to

start compressors with or without reversing valve operation

to produce Stage 1 Cooling (one compressor runs), Stage 2

Cooling (both compressors run) or Stage 1 Heating (both

compressors run).

Auxiliary (Electric) Heat control

The  RHH  unit can be equipped with  one or  two  auxiliary

electric heaters, to provide a second stage of heating. The

DFB will energize this Heating System for a Stage 2 Heating

Command  (heaters  operate  concurrently  with  compres

-

sor(s)  in  the  Stage  1  Heating  cycle),  for  an  Emergency

Heating sequence (compressors are off and only the elec

-

tric heaters are energized) and also during the Defrost cycle

(to eliminate a “cold blow” condition in the space).

X

C

G

W2

R

C

W2

G

W1

O/B/Y2

Y2

W1

R

Y1

Y1

   Typical
Thermostat
Connections

T
H
E
R
M
O
S
T
A
T

(Note 1)

(Note 2)

1.  Typical multi-function marking. Follow manufacturer’s configuration 

    instructions to select Y2. Do not configure for O output.

2.  W2 connection not required on units without electric heating.

   

Field Wiring

Central

Terminal

Board

NOTES:

DIP

SWITCHES

SPEED-UP

JUMPERS

Содержание RHH120

Страница 1: ...RING DIAGRAMS Economi er X Factory Option 27 SYSTEM COMPONENTS SPECIFICATIONS INPUTS OUTPUTS ENVIRONMENTAL ECONOMIZER MODULE WIRING DETAILS INTERFACE OVERVIEW ENTHALPY SETTINGS TWO SPEED FAN OPERATION...

Страница 2: ...t DANGER ELECTRICAL SHOCK HAZARD Failure to follow this warning will result in personal injury or death Before performing service or maintenance operations on unit turn off main power switch to unit a...

Страница 3: ...Enthalpy Sensor P 2 Position Damper w Barometric Relief U Ultra Low Leak Economizer w Barometric Relief OA Temp Sensor W Ultra Low Leak Economizer w Barometric Relief Enthalpy Sensor Outdoor Air Optio...

Страница 4: ...4 Specifications subject to change without notice 516 01 3604 04 Fig 2 Unit Dimensional Drawing Size 120 Units...

Страница 5: ...516 01 3604 04 Specifications subject to change without notice 5 Fig 2 Unit Dimensional Drawing Size 120 Units cont...

Страница 6: ...clearances LOCATION DIMENSION CONDITION A 48 in 1219 mm 18 in 457 mm 18 in 457 mm 12 in 305 mm Unit disconnect is mounted on panel No disconnect convenience outlet option Recommended service clearance...

Страница 7: ...o the check valve core s bottom O ring Install the fitting body and torque to 96 10 in lbs 10 9 1 Nm Do not exceed 106 in lbs 11 9 Nm when tightening INSTALLATION Jobsite Survey Complete the following...

Страница 8: ...ing 8 Make electrical connections 9 Install other accessories FRAME MOUNTED INSTALLATION Frame mounted applications generally follow the sequence for a curb installation Adapt the sequence as required...

Страница 9: ...516 01 3604 04 Specifications subject to change without notice 9 Fig 6 Roof Curb Details REV 50TM500827...

Страница 10: ...t is ready to be rigged and no longer will be lift ed by a fork truck the wood protector under the basepan must be removed Remove 4 screws from each base rail Wood protector will drop to the ground Se...

Страница 11: ...iscard the supply duct cover Install accessory CRDUCTCV001A00 to cover the vertical supply duct open ing Use the return duct cover removed from the unit end panel to cover the vertical return duct ope...

Страница 12: ...own form and assembled to a metal support tray using plastic stretch wrap Located in the return air compartment the assembly s metal tray is at tached to the basepan and also attached to the damper us...

Страница 13: ...e hood sides See Fig 17 and 18 Secure hood divider with 3 screws on each hood side The hood divider is also used as the bottom filter rack for the aluminum filter 5 Attach the post that separates the...

Страница 14: ...must be used to route the main power from the condenser end of the unit to either the factory option disconnect the bottom of the control box or the single point box accessory One inch conduit is pro...

Страница 15: ...1 4 in female spade connector from the 230 v connection and moving it to the 200 v 1 4 in male terminal on the prima ry side of the transformer Refer to unit label diagram for ad ditional information...

Страница 16: ...m deviation is 4 v Determine percent of voltage imbalance This amount of phase imbalance is satisfactory as it is below the maxi mum allowable 2 Operation on improper line voltage or excessive phase i...

Страница 17: ...socket re install 3 hex screws on the NFD enclosure 12 Re install the unit front panel Fig 29 Handle and Shaft Assembly for NFD CONVENIENCE OUTLETS Two types of convenience outlets are offered on RHH...

Страница 18: ...the bottom of the dis connect box For the load side wiring to the factory option disconnect route the wires through the hole on the right side of the disconnect Be sure to create a drip loop at least...

Страница 19: ...conduits Connect the power con duit to the internal disconnect if unit is so equipped or to the external disconnect through unit side panel Remove one of the two knockouts located on the bottom left...

Страница 20: ...ng valve position Reversing valves are ener gized during the cooling stages and the defrost cycle and de energized during heating cycles Once energized at the start of a cooling stage the reversing va...

Страница 21: ...DI 24 vac P2 4 CTB Y2 W1 Heat 1 DI 24 vac P2 7 CTB W1 W2 Heat 2 DI 24 vac P2 6 CTB W2 R Power 24 vac P3 1 CONTL BRD 8 C Common 24 vac P3 2 CONTL BRD 4 DFT 1 DI 24 vac DFT 1 to DFT 1 DFT 2 DI 24 vac D...

Страница 22: ...he bottom left side of the control box after removing one of the two knockouts in the corner of the box Using a connector at the control box to protect the wire as it passes into the control box Pull...

Страница 23: ...can be installed in the unit Use the wir ing procedure listed below for each heater as determined by the number of stages in the heater Single Stage Heaters Single stage heaters will have an orange a...

Страница 24: ...ce 516 01 3604 04 Fig 41 Accessory Electric Heater Control Connections NOTE Optional Outdoor Temperature Control at One Heater Stage Move either heater wire to this terminal and connect outdoor temper...

Страница 25: ...25 Specifications subject to change without notice 516 01 3604 04 Fig 42 Typical RHH Control Wiring Diagram...

Страница 26: ...26 Specifications subject to change without notice 516 01 3604 04 Fig 43 Typical RHH Power Wiring Diagram 208 230 3 60 unit shown...

Страница 27: ...module includes terminals for CO2 sensor Mixed Air sensor and an Outdoor Dry Bulb sensor Enthalpy and other options are available with bus sensors User Interface The interface provides status for norm...

Страница 28: ...040839 001 Rev G HJW10 www energy ca gov Certified FDD Product California Title 24 Part 6 Table 8 Economizer Module Left Hand Terminal Blocks LABEL TYPE DESCRIPTION Top Left Terminal Block MAT MAT 20k...

Страница 29: ...D display and a 4 button keypad on the front of the economizer controller Keypad Use the four navigation buttons see Fig 48 to scroll through the menus and menu items select menu items and to change p...

Страница 30: ...ETUP ADVANCED SETUP CHECKOUT ALARMS NOTE Some parameters in the menus use the letters MA or MAT indicating a mixed air temperature sensor location before the cooling coil This unit application has the...

Страница 31: ..._ F if not connected short or out of range DA TEMP _ _ _ F 0 F to 140 F 18 C to 60 C DISCHARGE AIR TEMPERATURE after Heating section Displays when Discharge Air sensor is connected and displays measu...

Страница 32: ...2 8 V 2 to 10 Vdc DCV MAXIMUM DAMPER POSITION Displays only if a CO2 sensor is connected Used for Vbz ventilation max cfm setpoint Displays 2 to 10 V if 3 sensors RA OA and MA In AUTO mode dampers con...

Страница 33: ...SET 45 F 35 F to 55 F 2 C to 13 C Incremented by 10 F SUPPLY AIR TEMPERATURE LOW LIMIT Temperature to achieve Freeze Protection close damper and alarm if temperature falls below setup value FREEZE POS...

Страница 34: ...r has failed or become disconnected check wiring then replace sensor if the alarm continues CO2 SENS ERR N A N A CO2 SENSOR ERROR CO2 sensor has failed gone out of range or become disconnected check w...

Страница 35: ...tion settings and checkout menu readings see Table 13 See Tables 14 21 for dry bulb and enthalpy sequence of operation With stage 3 delay STG3 DLY in Advanced setup menu second stage of mechanical coo...

Страница 36: ...v On 0 v Off VENTMIN to VENTMAX Closed On On High 24 v On 24 v On VENTMIN to VENTMAX Closed Yes Off Off High 0 v Off 0 v Off VENTMIN to VENTMAX Closed On Off High 0 v Off 0 v Off VENTMIN to Full Open...

Страница 37: ...O Y2 O OCCUPIED UNOCCUPIED None No Off Off Low 0 v Off 0 v Off MIN POS L Closed On Off Low 24 v On 0 v Off MIN POS L Closed On On High 24 v On 24 v On MIN POS H Closed Yes Off Off Low 0 v Off 0 v Off...

Страница 38: ...y for differential enthalpy The high limit boundary is ES1 when there are no stages of mechanical cooling energized and HL high limit when a compressor stage is energized Table 21 Enthalpy Operation w...

Страница 39: ...ly items that are configured are shown in the Checkout menu NOTE For information about menu navigation and use of the keypad see Interface Overview on page 29 To perform a Checkout test 1 Scroll to th...

Страница 40: ...mpling inlet to the sampling tube on the basepan 2 SPEED INDOOR FAN MOTOR SYSTEM WITH VARI ABLE FREQUENCY DRIVE FACTORY INSTALLED OPTION For details on operating RHH 2 stage cooling units equipped wit...

Страница 41: ...he belt span length by 1 64 For example if the belt span length is 32 inches 32 x 1 64 1 2 inch deflection BELT FORCE DEFLECTION METHOD Check the belt tension with a spring force belt force deflec tio...

Страница 42: ...ners www hvacpartners com TORQUE ALL SHEAVE SET SCREWS TO 110 130 in lbs SET SCREW SET SCREW STRAIGHT EDGE BELT SPAN BELT DEFLECTION FORCE SEE TABLE 1 DEFLECTION BELT SPAN 64 TABLE 1 TABLE 2 BELT CROS...

Страница 43: ...opeller for location in housing orifice and verify setscrew is tight Y N _____ Verify that fan sheaves are aligned and belts are properly tensioned Y N _____ Verify that scroll compressors are rotatin...

Страница 44: ...L2 _____________ L3 _____________ TEMPERATURES Outdoor air Temperature _____________ F DB Dry Bulb Return air Temperature _____________ F DB _____________ F Wb Wet Bulb Cooling Supply Air Temperature...

Отзывы: