iMAT 14
26
• It is imperative to read the permissible
mains voltage from the type plate (G)!
• Carry out installation works in accor-
dance with VDE 0100 / IEC 60364.
• Do not install when voltage is applied.
• Lift off domed cover (
A
) after removing
the 4 screws (
B
).
• Take power supply board (
C
) out of the
domed cover (
A
) after removing the
screw (
D
).
• Guide cables for power supply (
E
)
and potential-free contact (
F
) through
screwed cable fittings.
•
Terminals
VAC power supply
0.0 L
0.1 N
0.2 PE
• Connect potential-free contact (
F
) to
terminals 0.6 - 0.7 (fail safe) or 0.7 - 0.8
(open during malfunction).
• Pull cable (
E + F
) tight and screw down
cable fittings.
• Screw power supply board (
G
) with
screw (
D
) into domed cover (
A
)
• Plug ribbon cable (
H
) into control PCB
(
K
)
• If the individual wires have not been
screwed into the plug, they should be
attached as follows: 1.0 = brown
1.1 = blue
2.0 = black
• Put on top of cover (
A
) and tighten the
4 screws (
B
)
Please note:
The power supply board (
C
) is in a
reverse position (upside down) in the
domed cover (
A
).
During no-load operation, a voltage of up
to 36 VDC may be measured at terminals
1.0 and 1.1 (plug ribbon cable (
H
)).
english
H
B
A
E
C
F
D
K
24 VDC - voltage
VAC - voltages
0.8
normally open
0.7
common
0.6
normally closed
0.2
PE
Earth/Ground
0.1
N
Neutral
0.0
L
Phase
0.8
normally open
0.7
common
0.6
normally closed
6
±24V
+24 VDC (0V)
5
±24V
0V (+24 VDC)
Electrical installation • Instalación eléctrica
Installation electrique • Instalação elétrica
Содержание iMAT 14
Страница 36: ...iMAT 14 36 a b Maintenance Mantenimiento Entretien Manuten o...
Страница 41: ...iMAT 14 41...
Страница 42: ...iMAT 14 42...
Страница 43: ...iMAT 14 43...