iMAT 14
18
1. Feed pipe and fitting at least
¾"!
(internal dia > 0.7 inch)
2. No filters in feed line
3. Slope in feed line > 1%!
4. Only use ball valves with full open port!
5. Pressure: min. 18 psi!
(check type plate for correct pres-sure)
6. Short pressure hose!
7. For each yard of rising slope in the
outlet line, the required minimum pres-
sure will increase by 1.5 psi.
The rise of the outlet line must not
exceed 17 feet!
8. Collecting line min. ¾" with 1% slope
9. In the case of inflow problems, install
venting line.
english
Note:
Venting!
If the feed line cannot be laid with suffici
-
ent slope, it will be necessary to install a
venting line!
Note:
Pressure differences!
Each condensate source must be drained
separately!
Note:
Deflector area!
If drainage is to take place directly from a
line, it is advisable to arrange the piping
so that the air flow is diverted.
Installation • Instalación
Installation • Instalação
wrong • no correcto
incorrect • incorrecto
correct • correcto
correct • correcto