- 10 -
INDOOR UNIT
HEAT
EXCHANGER
(EVAPORATOR)
HEAT
EXCHANGER
(CONDENSER)
REVERSING
VALVE
COMPRESSOR
COOLING
HEATING
GAS SIDE
CAPILLARY TUBE
CHECK VALVE
LIQUID SIDE
OUTDOOR UNIT
• Cooling & Heating Models
MODEL
9K, 12K
(Cooling & Heating)
18K, 24K
(Cooling & Heating)
Pipe size(Diameter:ø)
Piping length
Elevation
Gas
Liquid
Rated
Max
Rated
Max
1/2"
1/4"
7.62m(25ft)
15m(50ft)
5m(16ft)
8m(26ft)
5/8"
3/8"
7.62m(25ft)
15m(50ft)
5m(16ft)
8m(26ft)
For installation over rated, *a proper quantity of refrigerant should be added for each meter.
Ex) 18K: When installed at a distance of 15m, 295g of
refrigerant should be added.
(15-7.62) x 40g = 295g
a proper quantity of refrigerant
9K, 12K
20g
18K, 24K
40g
Содержание HMC009KD
Страница 62: ...62 Schematic Diagram...
Страница 63: ...63...
Страница 68: ...2 Indoor Unit 18K 24K 3828AR7036Q 68 26 27 23 28 19 25 24 21 20 8 7 6 4 5 1 3 18 15 14 13 16 11 10 9 12 17 22 2...
Страница 83: ...P NO 3828AR7036Q Printed in Korea...