background image

 

 

 

 

   

2. 

Put the control box cover and grille frame back on using

the appropriate screws (Steps 

3

 and 

4

 of Wire the Indoor

Unit section). Put the 

grille

 insert back on.

REASSEMBLE

Fig. 8 — Indoor Unit Mounting

5

Fig. 9 — Outdoor Sensor Connection

1 2 3 4 5 6

ON

HEAT  PUMP

Model-12 DIP Switches location

(on the Control Box side)

HEAT  PUMP

Models-09,18 DIP Switches location

(on the Control Box side)

Inter unit cable clamp

TH1
TH2

TH3

Display

connection

Inter unit

terminal block

30 VDC

1 2 3 4 5 6

ON

1 2 3 4 5 6

ON

1 2 3 4 5 6

ON

COOLING ONLY

Model-12 DIP Switches location

(on the Control Box side)

COOLING ONLY

Models-09,18 DIP Switches location

(on the Control Box side)

Standard Dip Switches

status from the factory

(Heat pump only)

MAKE DRAINAGE CONNECTIONS

1. Connect the unattached end of the drainage tube to the

drainage hose outlet.

2. Seal the drainage connection to prevent leakage.

3. Make  sure  there  are  no  kinks,  “U”  bends  or  flattened

sections in the tube.

4. Check that the drainage functions properly. Fill the pan

below the unit’s coil with water and observe that it freely

drains out.

5. Make sure the drainage hose is at the bottom side of the

wall through-hole (see Fig. 5).

outdoor sensor cable 

towards

 the lower right hand corner

of the indoor unit.

WIRE THE INDOOR UNIT

2. Remove the unit's front panel by lifting the lower part

and pulling it gently outward and upward. See Fig. 6.

5. 

Pull downwards and 

outwardston

 the bottom of the grille

and gently raise the frame of 

the

 top of the unit.

3. 

Remove  the  two  screws  from  the  control  box  cover

and take off the cover. See Fig. 

7

. Save the

 screws to reassemble.

 

 

6 . 

Once  all  covers  are  off,  mount

 the unit onto the wall

 

 

 

   

mounting bracket. See Fig. 

8

.

NOTE: Leave covers off until after the Making Drainage

Connections section.

7 . 

Route  the  interconnecting  unit’s  electric  cable  and  the

Make  sure  that  all  wires and  screws  are  firmly  fastened.

Loose wires or connections can cause damage and present

a fire hazard.

1.

Strip the cables back

1

/

4

 inch.

8. 

Make sure that the wires are 

connected

 in accordance

with the wiring diagram on the inside of the unit front

cover or within this instruction manual.

9. Secure the control cables to the strain relief.

10. 

For heat pump systems only, connect the outdoor sensor

TH3 to its mating black terminal. See Fig.  9.

NOTE: In general wiring the indoor unit does not require the 

removal of the grille frame but in case of need do as follow: 

4. Remove the two screws from the air discharge opening.

Save the screws to reassemble. See Fig. 7A.

1. Connect the display connector to the display panel

printed circuit board.

Fig. 6 — Remove Grille Insert

Fig. 7 — Remove Control Cover

Mount the indoor unit on the mounting bracket

Gently push with

the arrow direction

1

2

FILTER

IR

RECEIVER

POWER/AIRCOND

TIMER

FILTER

IR

RECEIVER

POWER/AIRCOND

TIMER

Fig. 7A---Remove the screws from the air discharge opening.

Содержание DFS2A309J1A

Страница 1: ...d walls or ceilings Indoor and outdoor units should be installed at a Maximum line length of 50 ft and vertical separation of 30 ft Do not install indoor units near a direct source of heat such as dir...

Страница 2: ...ews 8 Outdoor Sensor Connecting Cable 1 Absorption Cushions 4 Electric Terminals 8 Remote Controller Rack 1 rack with 2 screws Remote Controller and Batteries 1 1 Owner s Manual 1 1 Available for HEAT...

Страница 3: ...21 1 4 X 10 7 16 35 7 16 X 25 3 16 X 12 9 32 43 5 16 X 25 3 16 X 15 3 4 NET WEIGHT lb 73 114 136 SEER Seasonal Energy Efficiency Ratio COOLING CAPACITY Btuh 9 000 11 600 19 000 SEER 13 0 13 0 13 0 HEA...

Страница 4: ...ge hose and control cable passage as shown in Fig 5 1 Mark the center of the hole to be drilled according to the re frigerant line routing used and dimensions shown in Fig 4 2 Make sure to drill outwa...

Страница 5: ...nd pulling it gently outward and upward See Fig 6 5 Pull downwards and outwardston the bottom of the grille and gently raise the frame of the top of the unit 3 Remove the two screws from the control b...

Страница 6: ...it s feets to prevent vibrations 2 Fasten the outdoor unit legs to the mounting base as shown in Fig 12 The cushion goes between the legs and the mounting base 3 Be sure that the unit is leveled MAKE...

Страница 7: ...SYSTEM When all the fittings are connected air must be expelled then refrigerant charge must be checked and adjusted Follow the steps below 1 Open the service port cap on the suction line valve large...

Страница 8: ...he MOCP for the outdoor unit is for both sections NOTE Specifications and performance data are subject to change without notice UNIT MCA MOCP FULL LOAD AMPS FAN MOTOR AMPS COMPRESSOR AMPS COMPRESSOR L...

Страница 9: ...BR GR YEL GREEN GREEN GREEN DC RTN 30 VDC HLTV RVS FAN RED 2 5 1 9 7 4 BLK YEL GR WH BRN OR 7130C J12 J6 J7 J8 FAN RVS COMP BLK J18 RED K6 K5 K1 K2 STEPPER MOTOR BLUE 30V WH K8 K9 K7 J11 FANH FAN T F...

Страница 10: ...OR 0 BLUE BR GR YEL GREEN GREEN GREEN DC RTN 30 VDC HLTV RVS FAN RED 1 6 5 4 3 2 BLK YEL GR WH BRN J12 J6 J7 J8 FAN RVS COMP BLK J18 RED K6 K5 K1 K2 STEPPER MOTOR BLUE 30V WH K8 K9 K7 J11 FANH FAN T F...

Страница 11: ...he unit becomes dirty or smudged wipe the out side of the panel with a soft dry cloth Use a mild liquid deter gent and wipe off carefully with a dry cloth To Clean Indoor Coil To clean the coil remove...

Страница 12: ...rmistor if necessary 3 Flashes Low Pressure Check system pressures Check refrigerant charge Check thermistors TH1 and TH2 for correct resistance 4 Flashes High Pressure Check system pressures Check re...

Страница 13: ...11 75 12 22 12 70 37 4 3 1 8 1 0 11 28 11 73 12 18 39 2 4 1 8 1 0 10 83 11 25 11 68 41 0 5 1 8 1 0 10 40 10 80 11 21 42 8 6 1 8 1 0 9 986 10 370 10 76 44 6 7 1 8 1 0 9 595 9 960 10 33 46 4 8 1 8 1 0 9...

Страница 14: ...118 4 48 2 3 1 3 2 192 2 227 2 364 120 2 49 2 3 1 3 2 122 2 206 2 291 122 0 50 2 3 1 3 2 055 2 137 2 220 123 8 51 2 3 1 3 1 990 2 070 2 151 125 6 52 2 3 1 3 1 928 2 006 2 085 127 4 53 2 3 1 3 1 867 1...

Страница 15: ...fan motor is blocked or turns slowly 1 Check voltage Repair wiring if necessary 2 Check indoor fan wheel if tight on motor shaft Tighten if necessary Indoor fan motor capacitor is burnt Replace indoo...

Отзывы: