background image

7

FILTER

IR

RECEIVER

POWER/AIRCOND

TIMER

FILTER

IR

RECEIVER

POWER/AIRCOND.

TIMER

INDOOR UNIT 09,12,18

PRESSURE

COMPRESSOR

IMPEDANCE

AUTO

OFF

REMOTE

FUSE

FILTER

IR

RECEIVER

POWER/AIRCOND

TIMER

POWER/AIRCOND. TIMER

IR RECEIVER

FILTER

1

2

3

4

5

6

7

8

9

HI speed

Comp

RV

S

Med speed

Low speed

Neutral

Contact

S(3ph)

T(3ph)

p.

Plastic Cover

L2

L1

115 VAC

1
2
3
4
5

30 VDC

FAN

RVS

COMP

(+30V)

DC RTN

6

TH1

TH2
TH3

*

1

2

3

4

5

6

FLARING AND CONNECTING REFRIGERANT LINES

1. Remove the protective cap from the flare fitting.
2. Remove the protective cap from the tubing and cut to the

required length. Be sure that the cut is perpendicular and

clean, without burrs.

3. Slip  the  flare  nut  on  the  tubing  and  flare  the  tube  end

using standard flaring tools.

4. Tighten the nut until resistance is met. Mark the nut and

the fitting. Using a suitable wrench tighten an additional

1

/

4

 turn. Use the following specified torque, according to

connection size:

Mixed-Phase line:

Suction line:

1

/

4

-in. — (12.3 ft-lb)

1

/

2

-in. — (36 ft-lb)

3

/

8

-in. — (29 ft-lb)

5

/

8

-in. — (47 ft-lb)

NOTE:  The  service  valves  on  the  outdoor  unit  must  remain

closed until all 4 connections have been made.

EVACUATE  TUBING  AND  CHARGE  THE  SYSTEM  —

When all the fittings are connected, air must be expelled, then

refrigerant charge must be checked and adjusted. Follow the

steps below.

1. Open the service port cap on the suction line valve (large

valve).

2. Connect  the  vacuum  pump  to  the  service  port  via  the

pressure gage and evacuate to 500 microns to eliminate

contamination and moisture.

3. Disconnect  the  vacuum  pump.  Unit  should  maintain

500 microns for 5 minutes.

5.  

Open the mixed-phase valve (small valve) with an Allen

wrench.

6.  O

pen the suction line valve (large valve) with an Allen

wrench.

7.  

The outdoor unit is supplied with sufficient R-22 refriger-

ant 

up to

 

25

 ft 

piping length

. Add 0.9 oz of refrigerant for

each additional 3 ft of tubing used.

8. Make sure that the valves are properly opened. Be careful

not to open them more than required as this may damage

the thread.

9. Replace the service port cap. Using refrigerant oil, lubri-

cate the cap beam and hand tighten until resistance is met.

Use a suitable wrench to tighten the cap by an additional

1

/

2

turn.

Power Supply —

See  Tables  4  and  5  for  electrical  data

and Fig. 13-16 for system wiring diagrams.

Leak Test —

Leak  test  all  fittings  with  appropriate  test

equipment.

Model  DFC2A/H 09

Fig. 12A --- Legs Mounting Base and Wiring

Outdoor Units

4.  Remove the service port  caps from the mixed-phase

valve and suction line valve

Fig. 12B --- Indoor unit Leds and Wiring

Содержание DFS2A309J1A

Страница 1: ...d walls or ceilings Indoor and outdoor units should be installed at a Maximum line length of 50 ft and vertical separation of 30 ft Do not install indoor units near a direct source of heat such as dir...

Страница 2: ...ews 8 Outdoor Sensor Connecting Cable 1 Absorption Cushions 4 Electric Terminals 8 Remote Controller Rack 1 rack with 2 screws Remote Controller and Batteries 1 1 Owner s Manual 1 1 Available for HEAT...

Страница 3: ...21 1 4 X 10 7 16 35 7 16 X 25 3 16 X 12 9 32 43 5 16 X 25 3 16 X 15 3 4 NET WEIGHT lb 73 114 136 SEER Seasonal Energy Efficiency Ratio COOLING CAPACITY Btuh 9 000 11 600 19 000 SEER 13 0 13 0 13 0 HEA...

Страница 4: ...ge hose and control cable passage as shown in Fig 5 1 Mark the center of the hole to be drilled according to the re frigerant line routing used and dimensions shown in Fig 4 2 Make sure to drill outwa...

Страница 5: ...nd pulling it gently outward and upward See Fig 6 5 Pull downwards and outwardston the bottom of the grille and gently raise the frame of the top of the unit 3 Remove the two screws from the control b...

Страница 6: ...it s feets to prevent vibrations 2 Fasten the outdoor unit legs to the mounting base as shown in Fig 12 The cushion goes between the legs and the mounting base 3 Be sure that the unit is leveled MAKE...

Страница 7: ...SYSTEM When all the fittings are connected air must be expelled then refrigerant charge must be checked and adjusted Follow the steps below 1 Open the service port cap on the suction line valve large...

Страница 8: ...he MOCP for the outdoor unit is for both sections NOTE Specifications and performance data are subject to change without notice UNIT MCA MOCP FULL LOAD AMPS FAN MOTOR AMPS COMPRESSOR AMPS COMPRESSOR L...

Страница 9: ...BR GR YEL GREEN GREEN GREEN DC RTN 30 VDC HLTV RVS FAN RED 2 5 1 9 7 4 BLK YEL GR WH BRN OR 7130C J12 J6 J7 J8 FAN RVS COMP BLK J18 RED K6 K5 K1 K2 STEPPER MOTOR BLUE 30V WH K8 K9 K7 J11 FANH FAN T F...

Страница 10: ...OR 0 BLUE BR GR YEL GREEN GREEN GREEN DC RTN 30 VDC HLTV RVS FAN RED 1 6 5 4 3 2 BLK YEL GR WH BRN J12 J6 J7 J8 FAN RVS COMP BLK J18 RED K6 K5 K1 K2 STEPPER MOTOR BLUE 30V WH K8 K9 K7 J11 FANH FAN T F...

Страница 11: ...he unit becomes dirty or smudged wipe the out side of the panel with a soft dry cloth Use a mild liquid deter gent and wipe off carefully with a dry cloth To Clean Indoor Coil To clean the coil remove...

Страница 12: ...rmistor if necessary 3 Flashes Low Pressure Check system pressures Check refrigerant charge Check thermistors TH1 and TH2 for correct resistance 4 Flashes High Pressure Check system pressures Check re...

Страница 13: ...11 75 12 22 12 70 37 4 3 1 8 1 0 11 28 11 73 12 18 39 2 4 1 8 1 0 10 83 11 25 11 68 41 0 5 1 8 1 0 10 40 10 80 11 21 42 8 6 1 8 1 0 9 986 10 370 10 76 44 6 7 1 8 1 0 9 595 9 960 10 33 46 4 8 1 8 1 0 9...

Страница 14: ...118 4 48 2 3 1 3 2 192 2 227 2 364 120 2 49 2 3 1 3 2 122 2 206 2 291 122 0 50 2 3 1 3 2 055 2 137 2 220 123 8 51 2 3 1 3 1 990 2 070 2 151 125 6 52 2 3 1 3 1 928 2 006 2 085 127 4 53 2 3 1 3 1 867 1...

Страница 15: ...fan motor is blocked or turns slowly 1 Check voltage Repair wiring if necessary 2 Check indoor fan wheel if tight on motor shaft Tighten if necessary Indoor fan motor capacitor is burnt Replace indoo...

Отзывы: