Split System Heat Pumps

Installation Instructions

2

Installation/ Startup

Information

FIRE, AND ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury, death and/or property damage.

Before performing service or maintenance operations

on unit, turn off unit main power switch and install

lockout tag.

!

These instructions must be read and understood

completely before attempting installation.

WARNING

Installation or repairs made by unqualified

persons can result in hazards to you and others.

Installation MUST conform with local building

codes or, in the absence of local codes, with the

the National Electrical Code NFPA 70/ANSI

C1-1999 or current edition and Canadian

Electrical Code Part 1 CSA C.22.1.

The information contained in this manual is

intended for use by a qualified service technician

familiar with safety procedures and equipped

with the proper tools and test instruments.

Failure to carefully read and follow all instruc-

tions in this manual can result in equipment

malfunction, property damage, personal injury

and/or death.

After uncrating unit, inspect thoroughly for hidden damage.

If damage is found, notify the transportation company

immediately and file a concealed damage claim.

Top skid assembly should be left in place until after the unit

is rigged into its final location.

REDUCED EQUIPMENT LIFE AND PERSONAL INJURY

HAZARD

mproper installation, adjustment, alteration, service or

maintenance can void the warranty

.

The weight of the condensing unit requires caution and

proper handling procedures when lifting or moving to

avoid personal injury. Use care to avoid contact with

sharp or pointed edges.

CAUTION

!

Safety Precautions

1. Always wear safety eye wear and work gloves when

installing equipment.

2. Never assume electrical power is disconnected. Check

with meter and disconnect.

3. Keep hands out of fan areas when power is connected

to equipment.

4. R--22 causes frost--bite burns.
5. R--22 is toxic when burned.

Locating The Outdoor Unit:

Check local codes covering zoning, noise, platforms.
If practical, avoid locating next to fresh air intakes, vent or

windows. Noise may carry into the openings and disturb

people inside.
Placement of the unit should be in a well drained area or

unit must be supported high enough so runoff will not enter

the unit.
Do not locate where heat, lint or exhaust fumes will be

discharged on unit (as from dryer vents).
Roof top installations are acceptable providing the roof will

support the unit and provisions are made for water

drainage and the noise or vibration through the structure.
Do not install the unit in a recessed or confined area where

recirculation of discharge air may occur.
Allow sufficient space for airflow clearance, wiring,

refrigerant piping, and servicing unit.

Содержание CHS180

Страница 1: ...Save This Manual for Future Reference 506 01 2002 01 5 07 07 Installation Start Up and Service Instructions Models CHS180 Split System Heat Pump Three Phase 208 230 460 Volt...

Страница 2: ...l after the unit is rigged into its final location REDUCED EQUIPMENT LIFE AND PERSONAL INJURY HAZARD mproper installation adjustment alteration service or maintenance can void the warranty The weight...

Страница 3: ...risdictions may prevail Side compressor 3 1 2 ft 1067 mm Side opposidte compressor 3 ft 914 mm Ends 2 ft 616 mm Top 5 ft 1524 mm Support Point Unit Total Weight 1 2 3 4 CHS180 803 158 243 244 158 365...

Страница 4: ...unit must be level and supported above grade by beams platform or a pad Platform or pad can be of open or solid construction but should be of permanent materials such as concrete bricks blocks steel...

Страница 5: ...door unit is above the outdoor unit the riser will function as a hot gas riser If the outdoor unit is above the indoor unit the riser is a suction riser Use a reduced diameter riser design and constru...

Страница 6: ...Failure to prevent collection of copper oxides may result in system component failures VAPOR LINE PIPING PROCEDURE Connect system vapor line to the vapor line stub on the outdoor unit and the vapor st...

Страница 7: ...must be grounded N EXAMPLE Supply voltage is 460 3 60 AB 452 v BC 464 v AC 455 v 452 464 455 Average Voltage 3 1371 3 457 Determine maximum deviation from average voltage Maximum deviation is 7 v Dete...

Страница 8: ...Split System Heat Pumps Installation Instructions 8 Fig 5 208 230 Volt Wiring Details...

Страница 9: ...Split System Heat Pumps Installation Instructions 9 Fig 5 208 230 Volt Wiring Details Cont with control box CHS180H N A...

Страница 10: ...Split System Heat Pumps Installation Instructions 10 Fig 6 460 Volt Wiring Details...

Страница 11: ...Split System Heat Pumps Installation Instructions 11 Fig 6 460 Volt Wiring Details Cont with control box CHS180L N A...

Страница 12: ...Split System Heat Pumps Installation Instructions 12 Fig 6 Auxiliary Box Diagram...

Страница 13: ...START UNIT The field disconnect is closed the fan circuit breaker is closed and the space thermostat is set above ambient so that there is no demand for cooling Only the crankcase heater will be ener...

Страница 14: ...compressor When TC2 closes demanding additional cooling the compressor loads to full load operation During heating compressor is always fully loaded When TH1 demands first stage heating the heat pump...

Страница 15: ...es the cleaning and the maintenance of standard coils Routine cleaning of coil surfaces is essential to minimize contamination build up and remove harmful residue Inspect coils monthly and clean as re...

Страница 16: ...Split System Heat Pumps Installation Instructions 16...

Страница 17: ...Split System Heat Pumps Installation Instructions 17...