Indoor Combustion Air
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in
personal injury or death.
Most homes will require additional air from
outdoors for combustion and ventilation. A space
with at least 50 cubic feet per 1,000 BTUH (4.8 cubic
meters per kW) input rating or homes with tight
construction may need outdoor air, supplied
through ducts, to supplement air infiltration for
proper combustion and ventilation of flue gases.
WARNING
Standard
and
Known-Air-Infiltration Rate
Methods
NFPA & AGA
Indoor air
is permitted for combustion and ventilation, if the
Stan-
dard
or
Known
−
Air
−
Infiltration Rate
Method is used.
The
Standard
Method may be used, if the space has no less vol-
ume than 50 cubic feet per 1,000 BTUH (4.8 cubic meters per kW)
input rating for all gas appliances installed in the space. The
stan-
dard
method permits indoor air to be used for combustion and ven-
tilation air.
The
Known Air Infiltration Rate
Method shall be used if the in-
filtration rate is known to be less than 0.40 air changes per hour
(ACH) and equal to or greater than 0.10 ACH. Infiltration rates
greater than 0.60 ACH shall not be used. The minimum required
volume of the space varies with the number of ACH and shall be
determined per
Table 2
or
Equations 1 and 2
. Determine the
minimum required volume for each appliance in the space, and
add the volumes together to get the total minimum required vol-
ume for the space.
Table 2
M
INIMUM SPACE VOLUME FOR 100% COMBUSTION AND VENTILATION AIR FROM INDOORS
Other Than Fan-Assisted Total
Fan-assisted Total
ACH
30,000 BTU
(8.79 kW)
40,000 BTU
(11.72 kW)
50,000 BTU
(14.65 kW)
50,000 BTU
(14.65 kW)
75,000
(21.98 kW)
100,000 BTU
(29.30 kW)
125,000 BTU
(36.63 kW)
150,000 BTU
(43.95 kW)
ft
3
(
m
3
)
0.60
1,050 (29.7)
1,400 (39.2)
1,750 (49)
1,250 (35)
1,875 (52.5)
2,500 (70)
3,125 (87.5)
3,750 (105)
0.50
1,260 (35.3)
1,680 (47.04)
2,100 (58.8)
1,500 (42)
2,250 (63)
3,000 (84)
3,750 (105)
4,500 (126)
0.40
1,575 (44.1)
2,100 (58.8)
2,625 (73.5)
1,875 (52.5)
2,813 (78.8)
3,750 (105)
4,688 (131.3)
5,625 (158)
0.30
2,100 (58.8)
2,800 (78.4)
3,500 (98)
2,500 (70)
3,750 (105)
5,000 (140)
6,250 (175)
7,500 (210.6)
0.20
3,150 (88.2)
4,200 (117.6)
5,250 (147)
3,750 (105)
5,625 (157.5)
7,500 (210)
9,375 (262.5)
11,250 (316)
0.10
6,300 (176.4)
8,400 (235.2)
10,500 (294)
7,500 (210)
11,250 (315)
15,000 (420)
18,750 (525)
22,500 (632)
0.00
NP
NP
NP
NP
NP
NP
NP
NP
NP = Not Permitted
Table 2
Minimum Space Volume
s were determined by using the
following equations from the National Fuel Gas Code ANSI
Z223.1/NFPA 54
−
2009, 9.3.3.2:
1.
For
other than fan
−
assisted appliances
such as a draft
hood
−
equipped water heater,
1000 BTUH
21 ft
3
(
I
other
)
Volume other
=
ACH
.293 kW
59 m
3
(
I
other
)
Required Volume other
ACH
2.
For
fan
−
assisted appliances
such as this furnace,
If:
I
other
= combined input of all
other than fan
−
assisted
appliances
in BTUH
I
fan
= combined input of all
fan
−
assisted appliances
in
BTUH
ACH
= air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the
Standar
d Method and to
the
Known Air Infiltration
Rate Method.
•
Adjoining rooms can be considered part of a space, if there
are no closable doors between rooms.
•
Combining spaces on the same floor level. Each opening
shall have a free area of at least 1 in.
2
/1,000 BTUH (22
cm
2
/kW) of the total input rating of all gas appliances in the
space, but not less than 100 in.
2
(645 cm
2
). Once opening
shall commence within 12” (604.8mm) of the ceiling and the
second opening shall commence within 12” (604.8mm) of the
floor. The minimum dimension of air openings shall be at least
3 in(76.2mm).
•
An attic or crawl space may be considered a space that freely
communicates with the outdoors provided there are adequate
ventilation openings directly to outdoors. Openings
MUST
re-
main open and
NOT
have any means of being closed off. Ven-
tilation openings to outdoors
MUST
be at least 1 square inch
of free area per 4,000 BTUH (5.5 cm
2
/kW) of total input rating
for all gas appliances in the space.
•
In spaces that use the
Indoor Combustion Air
Method, in-
filtration should be adequate to provide air for combustion,
ventilation and dilution of flue gases. However, in buildings
with unusually tight construction, additional air
MUST
be pro-
vided using the methods described in section titled
Outdoor
Combustion Air
Method
:
•
Unusually tight construction is defined as Construction with:
1. Walls and ceilings exposed to the outdoors have a continu-
ous, sealed vapor barrier. Openings are gasketed or
sealed and
2. Doors and openable windows are weather stripped and