background image

441 01 2314 06

Specifications are subject  to change without notice.

16

Piping with Street Elbows

1. Assemble the elbows so that the outlet of one(1) elbow is 90

°

from the inlet of the other. The elbows should be tight enough

to be leak proof. An additional 

1

/

turn will be required at the

end of step 2, see 

Figure 8

.

2. Screw elbow assembly into gas valve far enough to be leak

proof. Position elbow assembly so that the inlet of the elbow is

at the bottom of the gas valve. An additional 

1

/

2

 turn will be re-

quired in step 3. Turn open end of inlet elbow to face the right

side of the furnace (

1

/

4

 turn), see 

Figure 9

.

3. Turn assembly an additional 

3

/

8  

turn to position inlet near the

top of the gas valve and in line with gas opening on right side of

furnace, see 

Figure 7

 and 

Figure 10

.

Figure 8

25

23

23c

Elbows  (*8DNL)

Figure 9

Gas Valve with Elbows  (*8DNL)

Representative drawing only, some models may vary in appearance.

Figure 10

Gas Valve with Elbows  (*8DNL)

Representative drawing only, some models may vary in appearance.

4. Gas supply line then can be run directly into opening of elbow.

Piping with Close Nipples and Standard Elbows

1. Assemble elbows and nipples similar to street elbows shown

in 

Figure 8

.

2. Follow steps 2 through 4 

Piping with Street Elbows.

FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in

personal injury, death and/or property damage.
A flexible corrugated metal gas connector must be

properly installed, shall not extend through the side

of the furnace, and shall not be used inside the

furnace.
Black iron pipe shall be installed at the furnace gas

control valve and extend a minimum of 2

 (50.8mm)

outside furnace.

!

WARNING

Additional Propane Piping Requirements

Have a licensed Propane gas dealer make all connections at

storage tank and check all connections from tank to furnace.

If copper tubing is used, it 

MUST

 comply with limitation set in

local codes, or in the absence of local codes, the gas codes of

the country having jurisdiction.

Two

stage regulation of Propane gas is recommended.

FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in

personal injury, death and/or property damage.
A natural gas or Propane gas leak ignited by an

open flame or spark could result in personal injury,

death and/or property damage.
Natural gas is lighter than air and will rise.  Propane

gas is heavier than air and will settle and remain in

low areas and open depressions.
Thoroughly ventilate area and dissipate gas. Do

NOT use a match or open flame to test for leaks, or

attempt to start up furnace before thoroughly

ventilating area.

!

WARNING

Final Check

Test all pipes for leaks.

If orifices were changed, make sure they are checked for

leaks.

During pressure testing of gas supply piping system:

a. If test pressure does not exceed 

1

/

2

 psi (24 pa), isolate the

furnace from the gas supply piping system by closing the 

equipment shutoff valve.

b. If test pressure exceeds 

1

/

2

 psi (24 pa), the furnace and its

manual equipment shutoff valve must be disconnected

  from the gas supply piping system.

To check for leaks apply soap suds or a liquid detergent to

each joint. Bubbles forming indicate a leak.

Do not use an open flame to test for gas leaks. Fire or explo-

sion could occur.

Correct even the smallest leak at once.

Содержание C8DNL

Страница 1: ...injury TABLE OF CONTENTS SAFETY CONSIDERATIONS 2 Safe Installation Requirements 3 INSTALLATION 4 Combustion Ventilation Air 6 Gas Vent Installation 9 Venting Horizonta 10 Venting Chimney Adapter 12 Ga...

Страница 2: ...nformation This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNIN...

Страница 3: ...e ON setting ____ Fan Time OFF Setting ___ Manual Gas Shut Off Upstream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Calculated Firing Rate See Checks and A...

Страница 4: ...around supply and return air ducts Install correct filter type and size Unit MUST be installed so electrical components are pro tected from direct contact with water Safety Rules Your unit is built to...

Страница 5: ...ible material See Ductwork and Filter Sub base for Com bustible Floors 6 Maintain clearance for fire safety and servicing A front clear ance of 24 609 6mm required and 30 762mm recommen ded for access...

Страница 6: ...ion Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket and building joists studs or framing DIMENSIONAL INFORMATION Unit Capacity Cabinet Top...

Страница 7: ...gens that will result in safety and performance related problems and may harm the furnace These instances must use only out door air for combustion The following areas or types of structures may cont...

Страница 8: ...Not less than the sum of the areas of all vent connectors in the space The opening shall commence within 12 304 8mm of the top of the enclosure Appliances shall have clearances of at least 1 25 4mm f...

Страница 9: ...0 20 3 150 88 2 4 200 117 6 5 250 147 3 750 105 5 625 157 5 7 500 210 9 375 262 5 11 250 316 0 10 6 300 176 4 8 400 235 2 10 500 294 7 500 210 11 250 315 15 000 420 18 750 525 22 500 632 0 00 NP NP NP...

Страница 10: ...pipe as per mitted by the National Fuel Gas Code Code ANSI Z223 1 NFPA 54 2009 Sections 12 and 13 venting requirements in the United States or the National Standard of Canada Natural Gas and Pro pane...

Страница 11: ...st be lined with either Type B vent sized in accordance with NFGC tables 13 1 or 13 2 or a listed metal lining system sized in accordance with the NFGC Section 13 1 7 for a single appliance or 13 2 20...

Страница 12: ...dryer or water heater vent or other appliance s direct vent intake or exhaust N Clearance to the vent terminal of a dryer vent water heater vent or other appliances direct vent intake or exhaust O Cle...

Страница 13: ...s are for use with ONLY furnaces having a Chimney Adapter Kit number marked on the furnace rating plate WARNING If a clay tile lined masonry chimney is being used and it is exposed to the outdoors bel...

Страница 14: ...vent in a chase If a metal liner or Type B vent is used to line a chimney no other appliance shall be vented into the annular space between the chimney and the metal liner APPLIANCE APPLICATION REQUI...

Страница 15: ...anufacturer s installation instructions CHIMNEY INSPECTION CHART For additional requirements refer to the National Fuel Gas Code ANSI Z223 1 NFPA 54 2009 and ANSI NFPA 211 2006 Chimneys Fire places Ve...

Страница 16: ...ose to the furnace as possible where it is readily ac cessible Refer to Figure 7 FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Use wrench to h...

Страница 17: ...rnace Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2 50 8mm outside furnace WARNING Additional Propane Piping Requirements Have a licensed Propane gas de...

Страница 18: ...Box to alternate location and attach using two self tapping screws from bag 5 A wire tie may need to be cut for additional wire length 6 Apply two hole plugs from bag at left J Box location 7 Positio...

Страница 19: ...trical shorts of 24V wiring during installation service or maintenance may cause fuse to blow If fuse replacement is required use only a fuse of identical size 5 amp FUSE 25 24 98 Diagnostic Light Jum...

Страница 20: ...er is in the full heat or cool position Installation of locking type dampers is recommended in all branches or in individual ducts to balance system s air flows Non combustible flexible duct connector...

Страница 21: ...15 381 221 2 571 5 Subbase for Coil Box NAHH004SB 153 4 25 4 209 16 522 3 149 16 369 9 161 16 408 161 4 412 8 145 8 371 5 15 381 131 2 342 9 15 381 131 2 342 9 NAHH005SB 193 8 181 1 209 16 522 3 183...

Страница 22: ...e return air plenum above the furnace A filter rack is supplied with each furnace See Figure 17 Use either filter type Washable high velocity filters are based on a maximum air flow rating of 600 FPM...

Страница 23: ...d pull straight down at side of blower Pull out through right door opening 4 Vacuum clean or wash with warm water and dry thoroughly be fore replacing NOTE If filters are only suitable for heating app...

Страница 24: ...rol Remove manometer connection from manifold pressure tap and replace plug in gas valve 7 Check for leaks at plug Typical Gas Control Valve Figure 19 Regulator Adjustment Under Cap Inlet Pressure Tap...

Страница 25: ...in accordance with the Manufacturer s instructions and all applicable codes and requirements or in the absence of local codes the applicable national codes WARNING MANIFOLD PRESSURE AND ORIFICE SIZE F...

Страница 26: ...e burner compartment 2 Disconnect gas line from gas control valve so manifold can be removed 3 Disconnect wiring at gas control valve Be sure to note the proper location of all electrical wiring befor...

Страница 27: ...ply and return air registers as close to furnace as possible avoiding direct radiant heat from heat exchangers 2 Operate furnace for 10 minutes with all the registers and duct dampers open by using a...

Страница 28: ...he continuous fan option This connection is intended for the low speed motor tap and has a lower contact rating 8 amps than the heat and cool taps When the low speed blower lead is connected to this t...

Страница 29: ...continuously while there are no other blower demands from furnace control Fan demands from furnace control for heat cool or G will override hard wired speed tap NOTE 3 EAC is NOT active for hard wired...

Страница 30: ...c Codes See Figure 25 OFF 24VAC or 115VAC is off fuse is open Heartbeat Normal operation or no previous Diagnostic Code ON SOLID Soft Lockout Furnace Control Error 1 hr delay If code repeats immediate...

Страница 31: ...ubject to change without notice Save This Manual For Future Reference Downflow Models 8DNL050B12B2 8DNL075B12B2 8DNL075F16B2 8DNL100F14B2 8DNL100L20B2 8DNL125L20B2 Denotes Brand International Comfort...

Страница 32: ...han 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC Limits Controls Thermal Sensor oF oC Limit Control 300 149 See Parts List 300 149 See Parts List 300 149 See Par...

Страница 33: ...Liters per second Filter required for each return air inlet Airflow performance includes 1 25 4mm washable 600 FPM 3 0 m s max filter media See Table for bellyband location on motor 8DNL100F14 1 Exter...

Страница 34: ...441 01 2314 06 Specifications are subject to change without notice 33 Wiring Diagram 8DNL...

Страница 35: ...njury or property damage Consult a qualified installer service agency local gas supplier or your distributor or branch for information or assistance The qualified installer or agency must use only fac...

Отзывы: