Communication

 

Test

 

Once the ZT-2000 I/O device has joined the ZigBee network, the signal 

quality can be comfirmed by monitoring the status of the ZigBee Net LED 
indicators. If the LED indicator shows a steady light, communication with the 
ZT-2000 I/O device has been successfully established for data acquisition and 
control. 

ICP DAS also provides the “DCON Utility”, which can be used to simulate 

DCON/Modbus communication. This software can also be used to verify the 
device settings and ZigBee I/O functions. 

※ 

The 

DCON Utility

 can be dowmload from: 

http://ftp.icpdas.com/pub/cd/8000cd/napdos/driver/dcon_utility/

 

 

mulate I/O channel operating via using DCON Utility   

Si

1.

 

Launch DCON Utility and select the correct COM Port settings to connect the 
ZigBee Coordinator (ZT-2550/ZT-2570). 

2.

 

Clicking “Search” button will start searching which ZT-2000 I/O device is in the 
same ZigBee network. 

3.

 

If there is any ZT-2000 I/O devices displayed, double clicking the “module 
name” will start the I/O channels operated platform.

 

2

ICP

 

DAS,

 

ZT

2000

 

DIO

 

SERIES

 

Quick

 

Start,

 

Version

 

1.2.1

   

Page

 

7

 

Copyright

 

©

 

2013

 

by

 

ICP

 

DAS

 

Co.,

 

Ltd.

 

All

 

Rights

 

Reserved.

 

Содержание ZT-2053

Страница 1: ...he DIP switch of ZT 2000 I O device 2 Install the ZT Configuration Utility to configure the ZT 2000 coordinator CD Napdos ZigBee ZT_Series Utility http ftp icpdas com pub cd usbcd napdos zigbee zt_ser...

Страница 2: ...e value as other modules on the same ZigBee network Channel 0x00 0x01 0x0F Frequency MHz 2405 2410 2480 RF channels 0x04 0x09 0x0E or 0x0F are recommended because they do not overlap with the Wi Fi fr...

Страница 3: ...ng the external rotary switch and the DIP switches The ZT 2000 device should only be rebooted once the configuration is complete DIP Switch to the ZT 2042 ZT 2043 ZT 2053 ZT 2055 DIP Switch to the ZT...

Страница 4: ...ress of hardware switch is set to 0x00 it mens the address is using software configurations Refer the more detailed information at Sec 6 6 of user manual DIP Switch Number Item Status Explain OFF Vali...

Страница 5: ...n of the ZigBee coordinator has been completed Set the Pan ID and the RF Channel values for the ZT 2000 I O device to the same values as the network and then reboot the device The module will automati...

Страница 6: ...ZT 2570 Configurations of ZT 2000 I O Device 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 ON Number Item Status Explain 1 Address MSB OFF Address Node ID is 01 Rotation Switch 1 2 Protocol ON Use Modbu...

Страница 7: ...the device settings and ZigBee I O functions The DCON Utility can be dowmload from http ftp icpdas com pub cd 8000cd napdos driver dcon_utility mulate I O channel operating via using DCON Utility Si 1...

Страница 8: ...55x as a file b After clicking the Save Log icon enter the File Name and the File Path in the Windows Save dialog box Once the configuration has been successfully saved the following message will be d...

Отзывы: