PROFI-5053  PROFIBUS DAQ Module - QuickStart (Apr/2017)  

ICP DAS USA, Inc.

 | 

www.icpdas-usa.com

 | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717

 

 

 

Terminating Resistors 

 

In order to minimize the reflection effect of the signal transmission, PROFIBUS 
device has to fit with an active terminal resistor at both first node and last node. 
The connection of active terminating resistors is shown in above circuit diagram. 
The PROFI-5000 doesn’t have any terminating resistors inside. Therefore, users 
must add the terminator in external. In general, PROFIBUS connector has 
terminating resistors inside, and there is a switch to control the ON/OFF of the 
terminating resistors, as shown below. 

 
 
 
 

 

Terminator ON 

 

 

Terminator OFF 

 
 
 
 

Terminator Switch 

 
 
 
 
 
 
 
 
 
 

 

 

Node Address 

 

According to PROFIBUS specification, the station address which from 0 to 126 is 
valid, and the address 126 is a special address that supports the remote setting 
SSA telegram from Class 2 DP-Master. 

 

 

PROFI-5045/

 

PROFI-5050/

 

PROFI-5051/

 

PROFI-5052/ 

 

PROFI-5053/

 

PROFI-5055/

 

PROFI-5060 

 
 
 
 
 
 
 
 

 

 

Содержание PROFI-5000

Страница 1: ...Meaning 3 B Line Receive Transmit data plus 5 GND Power ground of active terminator 6 VP Power 5 volt of active terminator 8 A Line Receive Transmit data minus The PROFIBUS connector is a standard 9 p...

Страница 2: ...n and ERR LED will turn off The table explains the relationship between them Status Indicator Meaning Recommend solution ERR ON Offline Mode Check the address setting of RUN OFF module and DP master E...

Страница 3: ...diagram The PROFI 5000 doesn t have any terminating resistors inside Therefore users must add the terminator in external In general PROFIBUS connector has terminating resistors inside and there is a...

Страница 4: ...d the other one is low nibble of address Module applies the setting of rotary switch as its address if the address is valid While the address is invalid module loads the pre saved value from EEPROM Mo...

Страница 5: ...ita CA 90717 5 PROFI 5000 Setting and Module installation example for SIMATIC Step 7 The following steps can help users to set and apply the PROFI 5000 1 Address Setting 2 Load GSD file into the DP Ma...

Страница 6: ...DAQ Module QuickStart Apr 2017 ICP DAS USA Inc www icpdas usa com 1 310 517 9888 24309 Narbonne Ave Suite 200 Lomita CA 90717 6 d Install OK 3 Select I O modules a Choose PROFI 5000 b add I O module t...

Страница 7: ...e 200 Lomita CA 90717 7 c Modify system parameters and module parameters modify by user s preference System parameters Double click PROFI 5000 Module parameters Double click module 4 Download Setting...

Страница 8: ...as usa com 1 310 517 9888 24309 Narbonne Ave Suite 200 Lomita CA 90717 8 b Select PLC Download After the procedure finish DP Master will establish the connection with PROFI 5000 and execute program au...

Страница 9: ...PROFI 5053 PROFIBUS DAQ Module QuickStart Apr 2017 ICP DAS USA Inc www icpdas usa com 1 310 517 9888 24309 Narbonne Ave Suite 200 Lomita CA 90717 9 PROFI 5000 Quick Start Version 2 1 June 2013 8...

Отзывы: