LC-101H/LC-102H User Manual
- 7 -
I/O Specifications
Module
LC-101H
LC-102H
Digital Input
Channels
1
2
Type
Wet Contact, 90 ~ 240 V
AC
On Voltage Level
65 VAC
Off Voltage Level
56 VAC
Input Impedance
68 KΩ, 2W
Isolation
3000 VDC
Relay Output with Load Current Measurement
Channels
1
2
Type
Power Relay, Form C (SPDT N.O+N.C..)
Contact Rating
30 A @ 250 VAC
Max. Inrush Current
112A /1ms
Number of lighting
fixtures
(1).Incandescent Lamp: 40W/ 220VAC * 5 Sets
(2).LED(Electronic ballast): 40W/ 220VAC *8 Sets
Operate Time
15 ms Max
Release Time
22 ms Max.
Electrical Endurance
100,000 ops.
Mechanical Endurance
10,000,000 ops
AC Load Current
Measurement
Yes, 0 ~ 5 A range with 3% of FSR Accuracy.
Power-on Value
Yes
Safe Value
Yes