LC-101H/LC-102H User Manual
-
35 -
~AAEV
Enable/disable module calibration, V is 0 to disable and 1
to enable.
~AARD
read response delay time in ms in hex format
~AARDVV
set response delay time in ms, VV in hex format, 00 - 1E
Baud Rate Settings (CC)
Code
03
04
05
06
07
08
09
0A
Baud Rate 1200
2400
4800
9600
19200
38400
57600
115200
Data Format Settings (FF)
7
6
5
4
3
2
1
0
CU
CS
Reserved
Key
Description
CS
Checksum Settings
0: Disabled
1: Enabled
CU
Counter Update:
0: The counter is updated when there is a falling edge in the input signal.
1: The counter is updated when
there is a rising edge in the input signal.
Note
: All Reserved bits should be zero.
DIP Switch setting
1 Protocol
ON: DCON, OFF: Modbus RTU
2 Configuration ON: by software, OFF: by hardware
3 Address
ON: added by 16, OFF: added by 0
4
INIT mode
ON: INIT, OFF: Normal
Base address: 32 (0x20)