LC-101H/LC-102H User Manual
- 6 -
2. Hardware
2.1 Specifications
Module
LC-101H
LC-102H
Communication
Ports
1 x RS-485
Data Format
N,8,1/O,8,1/E,8,1/N,8,2
Baud Rate
Hardware Configuration: Fixed 9600 bps
Software Configuration: 1200 to 115200 bps
Protocol
Modbus RTU / DCON
Software
Function
Local and Remote Direct Control Relay ON/OFF and
Remote Status Monitoring
Node Addresses
32 to 63 for hardware configuration
LED Display
Status
1 LED as Power Indicator
EMS Protection
ESD (IEC 61000-4-2)
±4 kV Contact for each Terminal
EFT (IEC61000-4-4)
±4 kV for Power
SURGE(IEC 61000-4-5)
±2 kV for Power
Power
Reverse Polarity
Protection
Yes
Input Voltage Range
10 ~ 30 VDC
Consumption
1.9 W Max.
2.8 W Max.
Mechanical
Dimensions (W x L x H)
72 mm x 95 mm x 57 mm
Installation
DIN-Rail
Environment
Operating Temperature
-25 to +75°C
Storage Temperature
-30 to +80°C
Humidity
10 to 95% RH, Non-condensing