ISaGRAF WinCE ViewPAC User Manual , V.1.6 , 1/2017 by ICP DAS
12
COM 2
RS-485 (Data+, Data-) with internal self-tuner ASIC; 2500 VDC isolated
COM 3
RS-232 (RxD, TxD, CTS, RTS, DSR, DTR, CD, RI and GND); Non-isolated
MMI (Man Machine Interface)
LCD
3.5” TFT
(Resolution 320 x 240)
5.7” TFT
(Resolution 640 x 480)
10.4” TFT
(Resolution 800 x 600)
Touch Panel
-
Yes
Rubber Keypad
24 keys
6 Keys
-
Audio
Microphone-In and Earphone-Out
Earphone-Out
LED Indicators
3 Dual-Color LEDs
(PWR, RUN, LAN1, L1, L2, L3; L1 ~ L3 for User Programmable)
2 LEDs (PWR, RUN)
I/O Expansion Slots
Slot Number
3
Note: For High Profile I-8K and I-87K Modules Only
Mechanical
Dimensions
(W x L x H)
182 mm x 158 mm x 125 mm
293 mm x 231 mm x 129 mm
Installation
Panel Mounting
Ingress Protection
Front panel: IP65
Environmental
Operating
Temperature
-20 ~ +70°C
Storage
Temperature
-30 ~ +80°C
Ambient Relative
Humidity
10 ~ 90% RH (non-condensing)
Power
Input Range
+10 ~ +30 VDC
Isolation
1 kV
Capacity
12.5 W
Consumption
7.2 W
8.5 W
Protocols (Note that certain protocols require optional devices)
NET ID
1 ~ 255, user-assigned by software
Modbus TCP/IP
Master
Link to a max. of 100 devices that support the Standard Modbus TCP/IP Slave protocol
(
Modbus RTU/ASCII
Master
A max. of 10 ports: COM2, 3 and COM5 ~ 14. (To connect to other Modbus Slave devices.)
Support Multi-port.
(*)
Modbus RTU Slave
A max. of 5 ports: one of COM2/3, COM5 ~ 8. (For connecting ISaGRAF, PC/HMI/OPC Server
and HMI panels.)
(*)
Modbus TCP/IP
Slave
LAN1 and optional 2nd Ethernet Port in I-8135W support total up to 32 connections for
connecting ISaGRAF and PC/HMI. If one of the Ethernet port malfunctions, the other one
can still be used to connect to the PC/HMI.
Web HMI Protocol
Ethernet ports for connecting a PC running Internet Explorer.
User-defined
Protocol
Custom protocols can be applied at COM2~3 and COM5~14 using Serial communication
function blocks.
(*)
I-7000 & I-87K
RS-485 Remote I/O
One of COM2 or COM3 supports I-7000 I/O modules, I-87K base + I-87K Serial I/O boards,
or RU-87Pn + I-87K High Profile I/O boards as remote I/O. A max. of 255 I-7000/87K remote
I/O modules can connect to one PAC.
(*)
Содержание ISaGRAF VP-23W7
Страница 44: ......
Страница 118: ......
Страница 134: ...ISaGRAF WinCE ViewPAC User Manual V 1 6 1 2017 by ICP DAS 9 2 On line help of ICP DAS add on functions function blocks ...
Страница 176: ...ISaGRAF WinCE ViewPAC User Manual V 1 6 1 2017 by ICP DAS Ap 16 Appendix C Hardware Interface Dimension ...
Страница 177: ...ISaGRAF WinCE ViewPAC User Manual V 1 6 1 2017 by ICP DAS Ap 17 VP 23W7 23W6 Unit mm ...
Страница 178: ...ISaGRAF WinCE ViewPAC User Manual V 1 6 1 2017 by ICP DAS Ap 18 VP 25W7 25W6 Unit mm ...
Страница 179: ...ISaGRAF WinCE ViewPAC User Manual V 1 6 1 2017 by ICP DAS Ap 19 ...
Страница 180: ...ISaGRAF WinCE ViewPAC User Manual V 1 6 1 2017 by ICP DAS Ap 20 VP 41x7 41x6 Unit mm ...
Страница 185: ...ISaGRAF WinCE ViewPAC User Manual V 1 6 1 2017 by ICP DAS Ap 25 ...