I-7080, I-7080D, I-7080B, I7080BD User Manual (V 2.2) ------------------ 63
2.39
@AAEAN
Description
: Enable counter alarm(for alarm-mode 0). Refer to Sec.
1.8.2 for more information.
Syntax
: @AAEAN[chk](cr)
@ is a delimiter character
AA=2-character HEX module address, from 00 to FF
N=0
enable counter 0
1
enable counter 1
[chk]=2-character checksum, if checksum disable
no [chk]
(cr)=0x0D
Response
: valid command
!AA[chk](cr)
invalid command
?AA[chk](cr)
no response
syntax error or communication
error or address error
! is a delimiter character indicating a valid command
? is a delimiter character indicating a invalid command
AA=2-character HEX module address
[chk]=2-character checksum, if checksum disable
no [chk]
(cr)=0x0D
Example
:
command: @01EA0(cr)
response : !01(cr)
command: @01EA1(cr)
response : !02(cr)
Enable counter 0.
Enable counter 1.
7080/7080D