I-7080, I-7080D, I-7080B, I7080BD User Manual (V 2.2) ------------------ 29
2.5 ~AA1
Description
: Reset the module status. The module status will be
latched until ~AA1 command is sent. If the module status=4, all
output command will be ignored. Therefore the user should read
the module status first to make sure that the module status is 0. If
the module status is not 0, only ~AA1 command can clear the
module status.
Syntax
: ~AA1[chk](cr)
~ is a delimiter character
AA=2-character HEX module address, from 00 to FF
[chk]=2-character checksum, if checksum disable
no [chk]
(cr)=0x0D
Response
: valid command
!AA[chk](cr)
invalid command
?AA[chk](cr)
no response
syntax error or communication
error or address error
! is a delimiter character indicating a valid command
? is a delimiter character indicating a invalid command
AA=2-character HEX module address
[chk]=2-character checksum, if checksum disable
no [chk]
(cr)=0x0D
Example
:
command: ~010(cr)
response : !0104(cr)
command: @01DO00(cr )
response : !(cr)
command: ~011(cr)
response : !01(cr)
command: ~010(cr)
response : !0100(cr)
command: @01DO00(cr)
response : >(cr )
module status=0x04
host is down
clear module status
module status=0x00
Output command is ignored
Output command is OK
7080/7080D