I-7080, I-7080D, I-7080B, I7080BD User Manual (V 2.2) ------------------ 12
1.6 Quick Start
Refer to
“
I-7000 Bus Converter User Manual
”
chapter-5 for
the following functions:
module status unknown(Sec. 5.1), change address(Sec. 5.2)
change baud rate(Sec. 5.3), checksum enable/disable(Sec. 5.4)
Wire connection(Sec 2.4)
Test program TEST.EXE(Refer to
“
NAP7000S User
Manual
”
for details.
1.6.1 Frequency Input Measurememt
1.
Refer to Sec. 1.5.2 for wire connection. Power on and run test.exe
2.
press 2
3.
press $012[Enter]
Receive=!01500600
4.
press 2
5.
press %0101510600[Enter]
Receive=>!01
6.
press 2
7.
press $01B0[Enter]
Receive=!01
8.
press 2
9.
press #010[Enter]
Receive=>????????
10.
press 2
11.
press #011[Enter]
Receive=>????????
step 3: the status of I-7080 is COUNTER mode
step 5: change to frequency mode
step 7: select non-isolated input
step 9: frequency measurement of channel-0
step 11: frequency measurement of channel-1
Note: the command $01B1(step 7) can be used to select the iso-
lated input.(the command $01B2 and $01B3 are used for
the other selections)