HRT-710 User Manual (Version 1.24, June/2015) PAGE: 72
Figure 3-
3 ―Save to Device‖ function
(3) Check the
firmware version
of HRT-710 like Figure 3-4.
Figure 3-4 Firmware Version of HRT-710
(4) Follow the below steps according to the different firmware version of HRT-710.
[ 4.1 - The firmware version of HRT-710 is v1.5 or newer ]
[1] In firmware v1.5 or newer, HRT-710 provides the MB Address
1300 ~ 1459
(
Default
CMD(3)(S) Data for Module 0 ~ 15 in HRT-710
=> The detailed information refers
to the sector 4.3 of users’ manual) and users can map the CMD(3) data of HART
device to SCADA directly with these Modbus address 1300 ~ 1459.
[2] For the ―
Default CMD(3)(S) data of
Module 0
‖ in HRT-710, the mapped MB
address is
1300 ~ 1309
. The below MB/RTU client will use the ―
Modbus Poll
‖ tool
to show the CMD(3) data of HART device by polling Modbus address 1300 ~ 1309.
<1> Confirm the connection between HG_Tool and HRT-710 is disconnected.
<2> Set the ―
Modbus
‖ parameters like Figure 3-5.