HRT-710 User Manual (Version 1.24, June/2015) PAGE: 15
HART command interval
:
1000 ms
HART command timeout value
:
1000 ms
Auto. Polling
:
Enable
Retry count
:
3
[ Modbus Default Value ]
Baud rate
:
115200 bps
Date bits
:
8 bits
Stop bits
:
1 bit
Parity
:
None
Net ID
:
1
Protocol
:
Modbus RTU Slave
Swap mode
:
None
2.6 Jumper
There is a Jumper (JP4) in the HRT-710 module shown as Figure 13. The
jumper can provide HART bus with
250 Ω (1/4 W) resistor. When the pin 1&2
of JP4 is closed, the resistor will connect to HART bus. When the pin 2&3 of
JP4 is closed or JP4 without jumper connected, it will disconnect the resistor
from HART bus. By default, the pin1&2 of JP4 is closed. Please refer to
section 2.3.4 - HART connection for detail.
Figure 13
:
Jumper of the HRT-710