HRT-710 User Manual (Version 1.24, June/2015) PAGE: 100
Byte 10
:
uint8 Flags
Byte 11~13
:
uint24 Device ID number (MSB first)
Command 12: Read Message
Request data bytes
:
none
Response data bytes
:
2+24 = 26
[Index Format Description]
Byte 0
:
uint8 Response code 1
Byte 1
:
uint8 Response code 2
Byte 2~25
:
PA24 Message
Command 13: Read Tag, Descriptor, Date
Request data bytes
:
none
Response data bytes
:
2+21 = 23
[Index Format Description]
Byte 0
:
uint8 Response code 1
Byte 1
:
uint8 Response code 2
Byte 2~7
:
PA6 TAG Name
Byte 8~19
:
PA12 Descriptor
Byte 20
:
uint8 Day of month
Byte 21
:
uint8 Month of year
Byte 22
:
uint8 Year as offset to 1900
Command 14: Read Primary Variable Sensor Information
Request data bytes
:
none
Response data bytes
:
2+16 = 18
[Index Format Description]
Byte 0
:
uint8 Response code 1
Byte 1
:
uint8 Response code 2
Byte 2~4
:
uint24 Sensor Serial Number (MSB first)
Byte 5
:
uint8 Sensor limits unit
Byte 6~9
:
float Upper sensor limit
Byte 10~13
:
float Lower sensor limit
Byte 14~17
:
float Minimum span
Command 15: Read Primary Variable Output Information
Request data bytes
:
none
Response data bytes
:
2+17 = 19
[Index Format Description]
Byte 0
:
uint8 Response code 1
Byte 1
:
uint8 Response code 2
Byte 2
:
uint8 Alarm select code
Содержание HRT-710
Страница 1: ...HRT 710 User Manual Version 1 24 June 2015 PAGE 1 TM H R T 7 1 0 User s Manual Version 1 24...
Страница 32: ...HRT 710 User Manual Version 1 24 June 2015 PAGE 32 Figure 23 MBRTU send and receive data...
Страница 96: ...HRT 710 User Manual Version 1 24 June 2015 PAGE 96 8 Dimensions...
Страница 97: ...HRT 710 User Manual Version 1 24 June 2015 PAGE 97...