GW-7553-B / GW-7553-M PROFIBUS/Modbus TCP Gateway User Manual
(Version 1.35, May/2017)
PAGE: 66
PS:
Modbus command:
Query message
DA
FC
SA
(Hi)
SA
(Lo)
NO
(Hi)
NO
(Lo)
01
02
00
00
00
10
Response message
DA
FC
BC
DATA
01
02
02
FE
DC
DA: Device Address-0x01
FC: Function Code-0x02:read DI
SA(Hi): Start Address(Hi byte)-0x00
SA(Lo): Start Address(Lo byte)-0x00
NO(Hi): No. Of points(Hi byte)-0x00
NO(Lo): No. Of points (Lo byte)-0x10
BC: Byte Count-0x02
4.10 PROFIBUS DP-V1 Data exchange example—Modbus RTU
In this example a Modbus Master device simulated by a PC program sends query
message and receives response message from a PROFIBUS Master via the GW-
7553 gateway.
In the following examples the CIF50-PB PROFIBUS Master card from Hilscher is
used. The configuration and communication is done by the program “SyCon”
provided by Hilscher.
Step 1: Copy the GSD file and assign the GW-7553 a valid station address
(Please refer to the section 4.2 GSD file).