GW-7553-B / GW-7553-M PROFIBUS/Modbus TCP Gateway User Manual
(Version 1.35, May/2017)
PAGE: 39
C. Input Relay/Coil module parameters
:
●
Modbus Slave Device ID (M)
:
0~247
●
Start Address(M)
:
0~65535
●
NO. of Relay/Coil(M)
:
8*(n-1)+1 ~ 8*n Bits
n=Module size/Byte
●
Module Type(M)
:
Read DI/DO
●
TCP_Connect_Index(T)(M)
:
1~8
D. Input Register module parameters
:
●
Modbus Slave Device ID (M)
:
0~247
●
Start Address(M)
:
0~65535
●
Module Type(M)
:
Read AI/AO
●
Change Word Order
:
Enable/Disable (Even module only)
●
TCP_Connect_Index(T)(M)
:
1~8
Example 1:
If the user wants to read a Modbus digital input module (DI module), Device ID is
1, data address is 10010~10019, and data count is 10 via the first TCP connection.
In this case, the user can select an “Input Relay/Coil=> 2 Bytes module”, module
parameters are shown in the below:
Input Relay/Coil module parameters
:
●
Modbus Slave Device ID(M)
:
1
●
Start Address(M)
:
9
●
NO. Of Relay/Coil(M)
:
10
●
Module Type(M)
:
Read DI
●
TCP_Connect_Index(T)(M)
:
1
Example 2:
If the user wants to write a Modbus analog output module (AO module), Device
ID is 2, data address is 40001~ 40004 and data count is 4 via the second TCP
connection.
In this case, the user can select an “Output Register => 4 Words module”, module
parameters are shown in the below: