ET-2200 Series Ethernet I/O Modules
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-73 -
The table describes the parameters contained in the "
Connectivity Settings
" section.
Item
Description
Defaults
MQTT
Enables or Disables the MQTT connection function.
Disabled
Broker
The IP address or the Host Name for the MQTT broker.
N/A
Broker Port
The port number for the MQTT broker.
1883
Client Identifier
The client identifier uniquely identifies the MQTT client to the
MQTT broker, and consists of the “module name”+ “_”
(underscore character) + “the last 6 digits of the MAC address”
and cannot be changed.
User Name
This parameter is used when the MQTT broker requires
authentication. The length should be no more than 63 characters.
N/A
Password
This parameter is used when the MQTT broker requires
authentication. The length should be no more than 63 characters.
N/A
Reconnection
Interval
The time interval between attempts by the ET-2200 module to
connect to the broker if a connection failure occurs. The valid range
is 5 to 65000 seconds
10(s)
Keep Alive
Interval
The keep-alive mechanism is provided to ensure that both the
client and the broker are alive and the connection is still open.
If a Client doesn’t send any messages during the Keep Alive period,
it must send a PINGREQ packet to the broker to confirm its
availability. The broker must reply with a PINGRESP packet to also
indicate its availability. The broker will disconnect a client, which
doesn’t send a PINGREQ packet or any other message within one
and a half times of the Keep Alive Interval. The valid range is 5 to
65000 seconds.
20(s)
Main Topic
Name
The Topic Name is a combination of the Main Topic Name and the
Sub Topic Name. The Main Topic Name can be empty. The same
part of the Topic Names can be entered in the Main Topic Name
field to improve the processing efficiency of all Topic Names. A
shorter Topic Name also improves processing efficiency.
N/A
Update Settings
Click this button to save any revised settings to the ET-2200 device.