ET-2200 Series Ethernet I/O Modules
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-96 -
The following is an example of a
Push mode
configuration:
Enter
“2”
in the
“DI Count”
field. This means
DI x 2 of ET-2260 #1 module
is mapped to
DO x 2 of ET-2260 #2 module
.
5.1.2
Push Mode
1.
In the “Pair-connection Settings”, select
“PUSH”
from the “
Mode
” drop-down options.
2.
Enter the
IP address for ET-2260 #2 module
in the “
Remote IP
” field.
3.
Enter the
TCP Port for ET-2260 #2 module
in the “
Remote Port
” field.
4.
Enter a
DI Count Value for ET-2260 #1 module
in the “
DI Count
” field.
(Local DI to Remote DO).
5.
Select
Modbus protocol (e.g., “TCP”)
from the
“TCP/UDP”
drop-down options.
6.
Click the “
Submit
” button to complete the configuration.
Figure 5-1.6