ET-2200 Series Ethernet I/O Modules
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-127 -
4xxxx: AO Address (Base 0)
Starting
Address
Points
Description
Bits per
Point
Range
Access
Type
255
(0xFF)
1
CPU Reset Status
16
1 = Reset at Power-on
2 = Reset by the WDT
3 = Reset using the reset
command
R/W
257
(0x101)
1
Setsthe Host Watchdog
Timer (WDT)
16
<5:
Disabled
5 to 65535:
Enabled
(units: seconds)
0:
Default
If the ET-2200 series module
loses communication with the
host PC for more than the
period defined in the WDT
settings, the DO channels will
revert to their safe values and
the Host WDT Events Counter
will be increased by one.
R/W/F
258
(0x102)
1
Host WDT Events
16
Denotes how many Host WDT
Events have occurred since the
last CPU reset
R/W
259
(0x103)
1
Module Name
16
Module Name
R
263
(0x107)
1
Setsthe TCP Timeout
Value
16
<5:
Disabled
5 to 65535:
Enabled
(units: seconds)
0:
Default
R/W/F
264
(0x108)
1
Setsthe System Timeout
Value
16
<30:
Disabled
30~65535:
Enabled
(unit: second)
0:
default
R/W/F
Notes
“R”:
Read;
“W”:
Write;
“F”:
Setting is recorded in flash as default.
Warning:
Frequent writing to the Flash can cause it to become corrupt.